3.3.3 Electromagnetic disturbance
We recommend a minimum distance of 2m between the charger / converter and any potentially sensitive
equipment.
Use shielded cables for all the connections (*). The shielding should be earthed at both the transmitting and the
receiving ends.
Keep cable length and shielding connections to a minimum.
Route cables as close as possible to conductive parts ("loose" cables or loops should be avoided – cables should
be placed against the hull or walls).
Keep power cables separate from control cables (at least 200mm).
The cables should only supply power to this appliance; any deviation to power another appliance is prohibited.
(
)
*
This is a recommendation for installation rather than an obligation. The installing electrician should decide
whether or not to use shielded cable depending on the EMC environment.
setting-adjustment-indicators
3.4
The charger DC-POWER + can be configured in 3 different ways.
- Via Push-buttons (see section 3.4.1)
- Via Bluetooth (see section 3.4.2)
- Via CANBUS (see section 3.4.4.9)
3.4.1 Setting by push-buttons
The DC-POWER PLUS chargers are equipped with 2 parameter buttons for configuring the charger, including
battery type (see 3.4.1.1) and activation of BOOST and REFRESH modes (see 3.4.1.2).
A first short press unlocks the settings, and allows you to modify the parameters by pressing the buttons in
succession.
Each press on one of the buttons changes the parameter, and a LED indicates the charger's status.
Once you've made your settings, wait for 3 seconds and the charger will automatically save them. It flashes in
sequence: BOOST/ABSORPTION/FLOATING to let you know that saving is complete.