Alarm
A41
Description
The DC current is over the limits.
Possible
The UPS detected the DC current out of limits and switch off the
causes
Solutions
1. Check that there aren't short circuit in DC bus.
2. Check the battery current sensor.
3. Check the battery blocks.
4. If the alarm persists, contact our Technical Support Service.
Alarm
A42
Description
Failure of the redundant auxiliary power supply.
Possible
Internal fault.
causes
Solutions
1. Contact our Technical Support Service.
Alarm
A43
Description
UPS output current sensor has detected the peak current.
Possible
Load problem.
causes
Measuring circuit failure.
Solutions
1. Check the peak of the output current.
2. Check the output current sensor.
3. If the alarm persists, contact our Technical Support Service.
Alarm
A44
Description
The inverter is blocked due to the operation of the desaturation sensor
of the IGBT drivers.
Possible
Inverter bridge fault.
causes
Solutions
1. Reset the system.
2. If the alarm persists, contact our Technical Support Service.
Manuel de l'utilisateur de l'ASI
MAX DC BATTERY CURRENT
inverter, booster and disconnected the battery from the UPS.
LOST OF REDUND POWER SUPPLY
MAX LOAD CURRENT
INVERTER DESATURATION