Télécharger Imprimer la page

LEGRAND KEOR HPE 200 kVA Manuel De Fonctionnement page 214

Publicité

Les langues disponibles

Les langues disponibles

Alarm
A5
Description
The measured DC voltage is out of tolerance.
Possible
 The battery has reached the discharge voltage due to a power
causes
 Measuring circuit failure.
Solutions
1. Check the actual value of the measured DC voltage.
2. In case of mains failure, wait for the AC voltage to be restored.
3. Check which alarms are present and carry out the indicated
procedures.
4. Restart the device.
5. If the alarm persists, contact our Technical Support Service.
Alarm
A6
Description
The rectifier voltage is reduced to start a short controlled discharge of
the battery.
Possible
 A battery test has been started automatically (if set), or manually
causes
Solutions
1. Wait for the test to end, and check possible battery faults.
Alarm
A7
Description
The battery isolator is open.
Possible
 Battery isolator open.
causes
Solutions
1. Check the status of the battery isolator.
2. Check the functionality of the auxiliary contact of the isolator.
3. Check the connection between the auxiliary contact of the
isolator and the auxiliary terminals of the UPS (if provided).
4. If the alarm persists, contact our Technical Support Service.
Alarm
A8
Description
The battery is discharging.
Possible
 The battery is discharging due to a mains failure.
causes
 Rectifier failure.
Solutions
1. Check which alarms are present and carry out the indicated
2. If the alarm persists, contact our Technical Support Service.
Manuel de l'utilisateur de l'ASI
DC VOLTAGE FAULT
failure.
BATTERY IN TEST
by the user.
BCB OPEN
BATTERY DISCHARGE
procedures.
UPS user manual
Utilizzo dell'UPS
OMP06263 REV. D
53

Publicité

loading

Ce manuel est également adapté pour:

Keor hpe 300 kvaKeor hpe 80kw960572