M1 leaf opening and closing speed
Set the M1 travel speed (percentage of maximum speed).
F28
M2 leaf opening and closing speed
Set the M2 travel speed (percentage of maximum speed).
F29
M1 leaf opening and closing slowdown speed
Set the M1 slowdown speed during opening and closing (as a percentage of the maximum speed).
The parameter is only used with [Opening slowdown point of M1] or [Closing slowdown point of M1] functions
active.
For Stylo ME and Stylo RME motors it might be necessary to reduce the minimum voltage applicable to the
motor to achieve the desired slowdown percentage. See function [F45 - Reduction of speed].
F30
M2 leaf opening and closing slowdown speed
Set the M2 slowdown speed during opening and closing (as a percentage of the maximum speed).
The parameter is only used with [Opening slowdown point of M2] or [Closing slowdown point of M2] functions
active.
For Stylo ME and Stylo RME motors it might be necessary to reduce the minimum voltage applicable to the
motor to achieve the desired slowdown percentage. See function [F45 - Reduction of speed].
F31
Travel AST control
Adjust the obstruction detection sensitivity during the gate travel in percentage terms.
F34
Slowdown AST control
Adjust the obstruction detection sensitivity during slowdown in percentage terms.
The parameter is only used if the opening or closing slowdown point is active.
F35
Adjusting the partial opening
For single-leaf gates, it determines the partial opening percentage of the leaf with respect to the total travel.
For two-leaf gates, it determines the partial opening percentage of the M2 leaf with respect to the total travel.
100% = Pedestrian opening
F36
40% to 100% (Default 70%)
40% to 100% (Default 70%)
10% to 50% (Default 40%)
10% to 50% (Default 40%)
10% to 100% (Default 100%)
10% = minimum thrust and high obstruction sensitivity
100 % =maximum thrust and low obstruction sensitivity
10% to 100% (Default 100%)
10% = minimum thrust and high obstruction sensitivity
100 % =maximum thrust and low obstruction sensitivity
10% to 100% (Default 100%)