Installing The Positioner On Process Valves Belonging To Series 26Xx And 27Xx - Burkert TopControl Basic Guide Rapide

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Push the positioner, without turning it, onto the actuator until no
gap is visible on the form seal.
NOTE!
Too high torque when screwing in the fastening screw does
not ensure degree of protection IP65 / IP67.
▶ The fastening screws may be tightened to a maximum torque of
1.5 Nm only.
Attach the positioner to the actuator using the two side fastening
screws. In doing so, tighten the screws only hand-tight (max.
torque: 1.5 Nm).
Connection
pieces
Pilot air
ports
Actuator
Fig. 7:
Installing the positioner, series 2103, 2300 and 2301
Type 8694
Installation
Fastening
screws
max. 1.5 Nm
7.3
Installing the positioner on process
valves belonging to series 26xx and
27xx
Procedure:
Fig. 8:
Aligning the puck
Push the positioner onto the actuator. The puck must be aligned
in such a way that it is inserted into the guide rail of the positioner.
NOTE!
Damaged printed circuit board or malfunction.
▶ Ensure that the puck is situated flat on the guide rail.
Press the positioner all the way down as far as the actuator and
turn it into the required position.
english
Guide rail
Puck