4. Operation
Chg. cur. limiting coef. (C): The charging current limit is a multiple of the battery capacity. The value range is 0.05 to 0.25.
The default value is 0.15. Consult the specific Tripp Lite battery cabinet owner's manual for the recommended Coefficient
(Coef.) based on the S3M UPS model and Tripp Lite battery cabinet model.
Cell float voltage (V/Cell): The float voltage value range is 2.20 to 2.29 V/cell. The default value is 2.27 V/cell.
Cell boost voltage (V/Cell): The battery equalized voltage value range is 2.30 to 2.40 V/cell. The default value is 2.35 V/cell.
Aver Charging Duration (min): Boost charge time limit. The value range is 1 to 999 minutes. The default value is 240.
Consult the specific Tripp Lite battery cabinet owner's manual for the recommended Aver Charging Duration (min) based on
the S3M UPS model and Tripp Lite battery cabinet model.
Figure 4-31B: Battery Settings
EOD Battery Volt (V/Cell): End of discharge voltage. The value range is 1.60 to 1.90. The default value is 1.67.
Float Temp Compen Coef. (V/Cell/°C): Modify the voltage of compensation after enabling the switch. The value range is
0.001 to 0.007/cell. The default value is 0.003.
Boost Charge Setting: Boost charge setting is disable or enable. The default is enable.
No Battery Warning: When set to Disable, the buzzer will not sound. Set to Enable for audible battery warnings. The default is
enable.
Figure 4-31C: Battery Settings