5. Troubleshooting

If the UPS system is not functioning normally, check for errors in installation, wiring or operation. If all these aspects check out
with no problems, contact support at tripplite.com/support with the following information:
1. Product model name and serial number.
2. Description of the problem with details, such as LCD display information, LED statuses, etc.
Read this owner's manual carefully. The table below may help you solve the problem easily.
No. Problem
1
Utility is connected but the UPS
cannot be powered ON.
2
Utility normal but Utility LED
does not illuminate, and the UPS
operates at battery mode
3
The UPS does not indicate a
fault, but there is no output
voltage
4
Utility LED is flashing
5
Battery LED is flashing but there
is no charge voltage and current
6
Buzzer beeps every 0.5 seconds
and LCD displays "Output
Overload"
7
The UPS only works on Bypass
Mode
8
Cannot Power On
Possible reason
• Input power supply is not connected
• Input voltage low
• The input switch of the UPS is not switched
on
• The input breakers of the UPS are not
switched on
• Input cable is not connected securely
• Output cable is not connected securely
• Output breaker switch not on
Utility voltage exceeds UPS input range
• Battery breaker is not switched on
• Batteries are damaged
• Battery is connected in reverse
• Battery number and capacity are not set
correctly
Overload
The UPS is set to ECO mode, or the transfer
times to bypass mode are limited
• Battery switch is not properly closed
• Battery fuse is not open
• Battery is low
• Battery quantity is set incorrectly
• Power breaker in the rear panel is not
switched to ON position
72
Solution
• Measure if the UPS input voltage/frequency is
within the window
• Ensure UPS input is switched on
• Switch on the input breaker
• Make sure the input cable is connected
securely
• Make sure the output cable is connected
securely
• Switch on the output breaker
If the UPS operates in battery mode, pay
attention to the remaining backup time needed
for your system
• Switch on the battery breaker
• If batteries are damaged, replace entire
group of batteries
• Connect the battery cables correctly
• Go to the LCD setting for the battery number
and capacity and set the correct data
Remove some of the load
Set the UPS working mode to UPS type (non-
parallel), or reset the times of transferring to
bypass or restart the UPS
• Close the battery switch
• Change the fuse
• Recharge the battery
• Power on the UPS with AC to set the correct
battery quantity
• Switch on the power breaker