4. Operation
4. Click the Time & Period icon to change the current date and current time. Click on the text to input a new value. Click
Save Config to confirm the change.
Click the Back icon to return to the previous window. Click the Home Page icon to jump to the main page.
5. Click the Comm. Setting icon to update the UPS system's communication settings. Click on the text to select or input a
new value. Click Save Config to confirm the change.
Comm. Address: UPS communication ID. The address range is 1-15. The default value is 1.
Comm. Baud Rate: Available baud rate settings are 2400, 4800, 9600, 14400 and 19200. The default value is 9600.
Click the Back icon to return to the previous window. Click the Home Page icon to jump to the main page.
Figure 4-24: Date and Time Settings
Figure 4-25: Communication Settings
54