Over-Current Protection; Ups To Battery Cabinet Model Compatibility - Tripp-Lite SmartOnline S3M Serie Manuel Du Propriétaire

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3. Installation and Wiring

3.8.3 Over-Current Protection

CAUTION!
• Wiring must be performed by qualified professional personnel.
• Before wiring or making any electrical connection, ensure the power supplied to the input and output of the UPS is cut off
completely and the internal battery connectors are disconnected.
• When connecting the UPS to the utility AC power and bypass source, protective devices and 3-pole connectors must be
installed. The protective devices and 3-pole contactors must use approved components that meet safety certifications. The
thermo-magnetic circuit breakers should be IEC 60947-2 trip curve C (normal). Refer below for required protective devices:
25kVA UPS: 100A input circuit breaker required.
30kVA UPS: 125A input circuit breaker required.
50kVA UPS: 200A input circuit breaker required
60kVA UPS: 250A input circuit breaker required
80kVA UPS: 320A input circuit breaker required
100kVA UPS: 400A input circuit breaker required
• When connecting the critical loads to the UPS, a listed certified breaker must be installed between them. Refer to the below
for the required breakers:
25kVA UPS: 100A input circuit breaker required.
30kVA UPS: 125A input circuit breaker required.
50kVA UPS: 200A input circuit breaker required
60kVA UPS: 250A input circuit breaker required
80kVA UPS: 320A input circuit breaker required
100kVA UPS: 400A input circuit breaker required
• Check that the size, diameter, phase and polarity of each cable connecting to the UPS is correct. For the specifications of
input/output cables, refer to the table in section 3.10.1 Power Cables.

3.9 UPS to Battery Cabinet Model Compatibility

Battery Cabinets
BP240V09 /
with Batteries
Battery Cabinets
BP240V09-
with NO Batteries
S3M25K, S3M30K
S3M50K
S3M60K
S3M80K, S3M100K
Note: For battery cabinet breaker information, refer to the Owner's Manual for your battery cabinet.
09K
BP240V40
BP240V40-
BP240V40L-
NIB
NIB
No
Yes
No
No
No
No
No
No
BP240V40L
BP240V65
BP240V65-
NIB
NIB
Yes
Yes
Yes
Yes
No
No
No
No
23
BP240V65L
BP240V100
BP240V65L-
BP240V100-
NIB
NIB
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
BP240V100L
BP240V100L-
NIB
No
Yes
Yes
Yes

Publicité

Table des Matières
loading