Recommended Circuit Breakers - Tripp-Lite SmartOnline S3M Serie Manuel Du Propriétaire

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3. Installation and Wiring

3.10.2 Recommended Circuit Breakers

UPS Model
S3M25K
S3M30K
S3M50K
S3M60K
S3M80K
S3M100K
CAUTION!
Protective earth cable: connect each cabinet to the main ground system. For grounding connection, follow
the shortest route possible.
WARNING!
Failure to follow adequate earthing procedures may result in electromagnetic interference or in hazards
including electric shock and fire.
Component
Mains Input Circuit Breaker
Bypass Input Circuit Breaker
Output Circuit Breaker
Battery Circuit Breaker
Mains Input Circuit Breaker
Bypass Input Circuit Breaker
Output Circuit Breaker
Battery Circuit Breaker
Mains Input Circuit Breaker
Bypass Input Circuit Breaker
Output Circuit Breaker
Battery Circuit Breaker
Mains Input Circuit Breaker
Bypass Input Circuit Breaker
Output Circuit Breaker
Battery Circuit Breaker
Mains Input Circuit Breaker
Bypass Input Circuit Breaker
Output Circuit Breaker
Battery Circuit Breaker
Mains Input Circuit Breaker
Bypass Input Circuit Breaker
Output Circuit Breaker
Battery Circuit Breaker
Table 3.3: Recommended Input Front-End and Output Back-End Circuit Breakers
Specifications
100A 3P
100A 3P
100A 3P
160A 3P
125A 3P
125A 3P
125A 3P
200A 3P
200A 3P
200A 3P
200A 3P
320A 3P
250A 3P
250A 3P
250A 3P
400A 3P
320A 3P
320A 3P
320A 3P
600A 3P
400A 3P
400A 3P
400A 3P
600A 3P
26