Télécharger Imprimer la page

LEGRAND KEOR HPE 60 Manuel De Fonctionnement page 280

Publicité

Les langues disponibles

Les langues disponibles

Status
S8
Description
The inverter is synchronized with the MASTER UPS.
Operating
This status is only present on the SLAVE UPS units, and shows that the
condition
inverter is synchronized with the signal sent by the MASTER UPS.
Status
S10
Description
The rectifier is in standby mode.
Operating
The rectifier is off and ready to be started to charge the battery (Green
condition
Conversion algorithm).
Status
S11
Description
The inverter is in standby mode.
Operating
The inverter is off and ready to be started in case of anomaly of the bypass
condition
mains.
Status
S12
Description
The battery is in standby mode.
Operating
The battery static switch is open and the battery is disconnected from the
condition
DC bus.
Status
S14
Description
The battery is charging.
Operating
The battery static switch is closed and the battery is in the first phase of the
condition
I/U charging mode (DIN 41773), with constant current and increasing
voltage.
Status
S15
Description
The battery is charging.
Operating
The battery static switch is closed and the battery is in the second and final
condition
phase of the I/U charging mode (DIN 41773), with constant voltage and
decreasing current.
46
OMW07104 REV. A
UPS user manual
Manuel de l'utilisateur de l'ASI
Utilizzo dell'UPS
INV MASTER SYNC
RECT STANDBY (NOT AVAILABLE)
INV STANDBY (NOT AVAILABLE)
BATT STANDBY (NOT AVAILABLE)
BATT CHARGE I
BATT CHARGE U