OPERATING STATUS DEFINITION

Status
S1
Description
The rectifier section is working properly.
Operating
The rectifier supplies the inverter and keeps the battery charged.
condition
Status
S2
Description
The battery is connected to the UPS.
Operating
The battery is kept charged by the rectifier and is ready to feed the inverter.
condition
Status
S3
Description
The inverter voltage and frequency are within the allowed range.
Operating
The inverter is ready to feed the load.
condition
Status
S4
Description
The inverter feeds the load.
Operating
The load is fed via the static inverter switch.
condition
Status
S5
Description
The inverter is synchronized with the bypass.
Operating
The synchronization between the inverter and the bypass is locked, and the
condition
static switch can change over from one source to the other.
Status
S6
Description
The bypass voltage and frequency are within the allowed range.
Operating
The bypass line is ready for changeover in case of inverter failure.
condition
Status
S7
Description
Load fed by the bypass line.
Operating
The load is fed by the bypass via the static switch, waiting for the inverter to
condition
restart.
Manuel de l'utilisateur de l'ASI
BOOSTER OK
BATTERY OK
INVERTER OK
INVERTER --> LOAD
INV BYPASS SYNC
BYPASS OK
BYPASS --> LOAD
UPS user manual