5.1 STORING AND CLEANING OF THE SENSOR

In correct installation conditions the 8045 flow transmitter is maintenance-free. If
contamination or clogging should occur during operation the sensor can be cleaned
with water or another cleaning agent compatible with the PVDF and SS316L.
It is highly recommended to perform a calibration of the zero point 24 hours
after the cleaning of the electrodes, or in cases of changes of the fluid.
The current output is set to 22 mA in case of an electronic failure and at the
start-up of the device all parameters are set to factory setting values (§ 4.6).
The reasons for failure can be seen within "Display 'ERROR' - output current
22mA" in the trouble shooting guide below.
5.2

TROUBLE SHOOTING GUIDE

If any problems persist, please contact your local Bürkert subsidiary or
return the product with a full explanation of the problem.
This section is designed to assist with problems which may occur during installation or
operation. If in doubt please do not hesitate to contact you local Bürkert subsidiary.
Faults
The transmitter does not work
Transmitter connected
Power supply on terminal + and - ok?
Power supply between 18-36VDC?
Power supply regulated
(oscillations rate ≠ ±5%?)
Fuse OK
Switch on
Transmitter programming/testing unavailable
Internal switch 2 'Locked'?
Display 'ERROR' - output current 22mA
Display at the start-up (EEPROM failure)?
Error at each start-up?
Display after validation of the menu
(EEPROM failure)
Failure at each validation of the menu?
Fluctuating display
Inappropriate filter ?
Air bubbles in the fluid
The electrodes are dirty
Are the electrodes passivated
Fluid Control Systems

MAINTENANCE

Status
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
34
Actions
Connect the device
Check the connection
Change power supply
Change power supply
Change the fuses
Set the switch ON
Set switch 2 to „unlock".
Restart the device
Return the device
Configure the device again
Return the device
Increase the filter or
select slow mode filtering.
Set slow mode filtering
Clean the electrodes
Install the transmitter into
the fluid 24hr before use
3.3
3.3
----
----
----
----
3.4.1
----
----
4.4
----
4.4.7
4.4.7
5.1
3.1
8045