Model THAEY (400-3-50)
Nominal cooling capacity (*)
Nominal cooling capacity (**)
Nominal heating capacity (+)
Nominal heating capacity (++)
E.E.R. (*)
E.E.R. (**)
E.S.E.E.R.
E.S.E.E.R.+
C.O.P. (+)
C.O.P. (++)
Sound pressure (***)
Sound power level (****)
Scroll/step compressor
Fans
Exchanger water contents
Water side exchanger nominal water flow (*)
Motor-driven pump useful static pressure (P/L installation) (*)
Motor-driven pump useful static pressure (T/H installation) (*)
Water tank contents (T and H installation)
R410A refrigerant charge
Polyester oil charge
Electrical data
Absorbed power (during summer operation) (*) (●)
Absorbed power (during summer operation) (**) (●)
Absorbed power (during winter operation) (+) (●)
Absorbed power (during winter operation) (++) (●)
Pump absorbed power (P and T installation)
Pump absorbed power (L and H installation)
Electrical power supply
Auxiliary power supply
Nominal current (during summer operation) (*) (■)
Nominal current (during summer operation) (**) (■)
Nominal current (during winter operation) (+) (■)
Nominal current (during winter operation) (++) (■)
Maximum current (■)
Starting current
Pump absorbed current (P and T installation)
Pump absorbed current (L and H installation)
Dimensions
Width (L)
Height (H) P and L installation
Height (H) T and H installation
Depth (P)
Water connections
(*) In the following conditions: condenser input
air temperature 35°C; chilled water
temperature 7°C; temperature differential at
evaporator 5°C.
(**) In the following conditions: condenser inlet
air temperature 35°C; chilled water temperature
18°C; temperature differential at evaporator
5°C.
(+) In the following conditions: evaporator inlet
air temperature 7°C D.B., 6°C W.B.; hot water
temperature 45°C; temperature differential at
the condenser 5°C.
(++) In the following conditions: evaporator inlet
air temperature 7°C D.B., 6°C W.B.; hot water
temperature 35°C; temperature differential at
the condenser 5°C.
ALLEGATI / ENCOLSED DOCUMENTS / ANNEXES / ANLAGEN / ANEXOS
(**!) Sound pressure level in dB(A), measured
at a distance of 5 m from the unit, with a
directionality factor of 2.
(****) Sound power level in dB(A) on the basis
of measurements made in compliance with the
UNI EN-ISO 3744 standard and Eurovent 8/1.
(■) Current absorbed without motor-driven
pump.
(●) Power absorbed without motor-driven pump.
N.B.:
The calculation of the E.E.R. and C.O.P. does
not take the pump absorption into account.
To obtain the total power and the total currents,
add the relative power and current values
absorbed by the motor-driven pumps.
91
107
109
kW
6,9
8,8
kW
9,3
12,2
kW
7,5
9,7
kW
8,3
10,9
2,58
2,66
3,54
3,56
2,77
3,16
3,07
3,50
2,71
2,83
4,19
4,21
dB(A)
47
47
dB(A)
69
69
No.
1/1
1/1
No. x kW
1 x 0.14
2 x 0.14
l
0,45
0,58
l/h
1213
1582
kPa
55/86
85
kPa
54/73
76
l
19
19
See serial No. plate
See compressor plate
kW
2,67
3,32
kW
2,61
3,43
kW
2,77
3,41
kW
1,98
2,60
kW
0,18
0,29
kW
0,29
-
V-ph-Hz
400-3-50
V-ph-Hz
230-1-50
A
3,0
4,8
A
3,5
5,3
A
3,8
4,8
A
4,3
5,3
A
7,3
8,6
A
35
48
A
1,12
1,40
A
1,40
-
mm
990
990
mm
905
1085
mm
905
1290
mm
380
380
Ø
1"G
1"G
H
111
11,1
15,5
12,4
13,5
2,62
3,54
3,15
3,49
2,78
4,16
47
69
1/1
2 x 0.14
0,76
1995
75
72
30
4,25
4,39
4,42
3,24
0,29
-
6,5
7,2
6,6
7,3
11,4
64
1,40
-
990
1085
1290
380