Télécharger Imprimer la page

LEGRAND KEOR HPE Manuel De Fonctionnement page 56

Keor hpe 60-160 kva
Masquer les pouces Voir aussi pour KEOR HPE:

Publicité

Les langues disponibles

Les langues disponibles

Installation and start-up of KEOR HPE UPS 60÷160 kVA
Installation et démarrage de l'ASI KEOR HPE 60÷160 kVA
Installazione e avviamento KEOR HPE UPS 60÷160 kVA
Power (kVA)
Input fuses [A]
Rectifier
Bypass
Phase conductor cross sect.
2
[mm
]
Rectifier
Bypass
Output
Battery
Neutral conductor sizing
Linear load
NON-linear load
Earth conductor cross sect.
2
[mm
]
Power connections
Type
Conductor max. cross section [mm
Max. number of conductors
Fixing bolt dimensions
Tightening torque [Nm]
(1)
The terminal can house two parallel conductors provided they are terminated with pin connectors
The sections given in the table above are indicative only. The cables have been designed according
to the standard CEI-UNEL35024/1, using the following data:
 70° C rated PVC copper cables
 ambient temperature equal to 40° C
 maximum length of the cables equal to 30 m (voltage drop < 0,5%)
 cables laid in cavities of structures or solid bottom cable trays
The given cross sections do not take into account the overload currents allowed by each line, which
are detailed in the product Technical Specification.
The UPS manufacturer is not responsible for the correct sizing of the device supply and output lines
for which the plant conditions and operating temperatures, which are specific of each electrical
installation, must be taken into account.
Power (kVA)
Rectifier input [A]
Bypass input / Output [A]
Battery [A]
(1)
Values referred to 400Vac rated voltage
(2)
For the overload values refer to the Technical Specification
Details of the electrical connections
4x (1x50) 4x (1x70) 4x (1x95)
4x (1x35) 4x (1x50) 4x (1x70)
4x (1x35) 4x (1x50) 4x (1x70)
3x (1x35) 3x (1x70) 3x (1x95)
2
]
4 ÷ 4,5
Rated current (at full load and battery recharging)
(1)
(1) (2)
60
80
125
160
100
125
Same as the phase conductor
1,5 x phase conductor cross section
25
35
Screw terminals
50
95
1 (2)
(1)
-
8 ÷ 15
60
80
109
140
87
115
100
133
100
125
200
225
160
200
4x (1x95)
4x (1x95)
4x (1x95)
3x (1x95)
50
50
Aluminiun bars
150
2
M10
42 ÷ 53
100
125
170
214
144
180
166
208
OML46086 REV. I
160
315
250
4x (1x150)
4x (1x120)
4x (1x120)
3x (1x150)
95
160
267
231
266
31

Publicité

loading

Ce manuel est également adapté pour:

Omb81275Oml46086Omg38225