Télécharger Imprimer la page

Setting Date And Time; Display Language Setting; New Battery Installation; Battery Configuration - LEGRAND KEOR HPE Manuel De Fonctionnement

Keor hpe 60-160 kva
Masquer les pouces Voir aussi pour KEOR HPE:

Publicité

Les langues disponibles

Les langues disponibles

6.1

SETTING DATE AND TIME

Date and time may be set via the CLOCK menu.
CLOCK SETTINGS
DD-MM-YY
Setting the current date and time correctly
The correct setting of the date and time is essential for the recording of the event log.
6.2

DISPLAY LANGUAGE SETTING

The table below shows the languages which can be set for the display.
Parameter
LANGUAGE
The parameters are changed via the arrow buttons (
used to confirm the entry.
6.3

NEW BATTERY INSTALLATION

The NEW BATTERY INSTALLATION menu is used in case battery circuit breaker BCB is not closed,
when requested, in the start-up phase. In this case the system will start considering the battery
completely discharged and activating the alarm "A10 – BATTERY FAULT".
To set the battery autonomy to 100% it is necessary to access the menu and press the
confirm.
6.4

BATTERY CONFIGURATION

In case the UPS has been tested without knowing the characteristic data of the storage battery, the
BATTERY CONFIGURATION menu allows to set such data. In particular, the following data can be set:
 Battery capacity in Ampere-hours (Ah)
 Recharging current in Amperes (A)
 Nominal autonomy in minutes
34
OMG38225 REV. F
UPS user manual
Manuel de l'utilisateur de l'ASI
Utilizzo dell'UPS
The single digits can be modified via the arrow
keys (
hh : mm
(ENTER).
Standard
Range
ITALIAN
GERMAN
FRENCH
ENGLISH
ITALIAN
PORTUGUESE
SPANISH
POLISH
TURKISH
/
) and confirmed by pressing
/
) to increase the digits, and the
button is
button to

Publicité

loading

Ce manuel est également adapté pour:

Omb81275Oml46086Omg38225