Alarm
A17
Description
The load is blocked on the bypass line.
Possible
 Very frequent changeovers due to load in-rush currents.
causes
 Static switch problems.
Solutions
1. Reset the system.
2. Check the in-rush currents of the loads.
3. If the alarm persists, contact our Technical Support Service.
Alarm
A18
Description
The manual bypass isolator is closed.
Possible
 Manual bypass isolator closed.
causes
Solutions
1. Check the status of the manual bypass isolator.
2. Check the functionality of the auxiliary contact of the isolator.
3. If the alarm persists, contact our Technical Support Service.
Alarm
A19
Description
The output isolator is open.
Possible
 Output isolator open.
causes
Solutions
1. Check the status of the output isolator.
2. Check the functionality of the auxiliary contact of the isolator.
3. If the alarm persists, contact our Technical Support Service.
Alarm
A20
Description
The current sensor has detected an overload at the output. If the alarm
persists, the thermal image protection will be activated (alarm A21).
Possible
 Output overload.
causes
 Measuring circuit failure.
Solutions
1. Check the loads connected to the UPS output.
2. Contact our Technical Support Service.
Manuel de l'utilisateur de l'ASI
RETRANSFER BLOCK
MBCB CLOSED
OCB OPEN
OVERLOAD
UPS user manual