6.7

BATTERY TEST

The BATTERY TEST menu allows to carry out a short discharge test of the battery. In case the battery is
not efficient, the alarm "A10 – Battery fault" is generated at the end of the test.
BATTERY TEST?
BATTERY TEST?
SPECIAL
BATTERY TEST
Possible loss of supply
This test can affect the continuity of supply to the loads if the battery is not fully charged.
6.8

SYSTEM RESET

The UPS is equipped with internal protections which block the system or some of its sections. The alarm
can be cleared and normal operation can be resumed via the RESET menu. In case the failure persists,
the UPS will return to the previous failure condition.
In some cases the RESET is necessary to simply reset a failure signal, then the UPS will resume
operation.
RESET DEVICE?
RESET DEVICE?
SPECIAL
RESET
Manuel de l'utilisateur de l'ASI
NO
(1x)
YES
NO
(1x)
YES
UPS user manual
Utilizzo dell'UPS
The value on the second line is ready to be
changed
The parameter is changed. The change is
confirmed by pressing
The system performs a reset and returns to the
previous screen
The value on the second line is ready to be
changed
The parameter is changed. The change is
confirmed by pressing
The system performs a reset and returns to the
previous screen
(ENTER)
(ENTER)
OMG38225 REV.F
37

Publicité

loading

Ce manuel est également adapté pour:

Omb81275Oml46086Omg38225