Télécharger Imprimer la page

Mimic Panel Led's - LEGRAND KEOR HPE Manuel De Fonctionnement

Keor hpe 60-160 kva
Masquer les pouces Voir aussi pour KEOR HPE:

Publicité

Les langues disponibles

Les langues disponibles

4.2

MIMIC PANEL LED'S

Picture 9 – UPS mimic panel
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
LED 9
LED 10
Manuel de l'utilisateur de l'ASI
AC line on rectifier input within tolerance
GREEN
AC mains failure / Wrong phase rotation
GREEN
AC bypass line within tolerance
GREEN
Wrong phase rotation
GREEN
AC bypass line out of tolerance / failure
OFF
Rectifier off or faulty
GREEN
DC voltage out of tolerance
RED
Rectifier on and DC voltage within tolerance
GREEN
Circuit breaker BCB closed and battery charging
GREEN
Battery discharging or under TEST
GREEN
Circuit breaker BCB open
ORANGE
Battery fault (following a battery test)
RED
Battery not available
OFF
Inverter voltage within tolerance and static switch closed
GREEN
Inverter overload or short-circuit
GREEN
Inverter off or voltage out of tolerance
OFF
Re-transfer blocked
ORANGE
Static bypass switch closed
ORANGE
Static bypass switch open
OFF
Output circuit breaker OCB closed
GREEN
Output circuit breaker OCB open
OFF
Manual bypass switch MBCB closed
ORANGE
Manual bypass switch MBCB open
OFF
Emergency power off (EPO) activated
RED
Normal operation
OFF
Maintenance request (slow blinking)
ORANGE
Critical alarm (fast blinking)
ORANGE
Normal operation
OFF
UPS user manual
Utilizzo dell'UPS
OMG38225 REV.F
23

Publicité

loading

Ce manuel est également adapté pour:

Omb81275Oml46086Omg38225