4.3.1.4.3Temp protections
RVT provides 8 bank temperature protections by eight temperature probes. Each
temperature probe protection level can be set independently. When any one of the eight
the temperature protection levels is reached.
-
all the capacitor steps are switched off
-
an alarm message appears on the display
the alarm relay is activated ( NO opens / NC closes )
-
-
the icons
4.3.1.4.4Temp warnings
RVT provides 8 bank temperature warnings by eight temperature probes. Each
temperature probe warning level can be set independently. When any one of the eight
temperature warning level is reached.
-
the fan / warning relay will be activated: the NO contact will close
-
the icon
and
are highlighted
Figure 42: RVT temperature protection settings
is highlighted
Figure 43: RVT temperature warning settings
Power Factor Controller RVT ç Measurements and Settings 49