Télécharger Imprimer la page

ABB RVT6 Instructions D'installation, D'utilisation Et D'entretien page 26

Publicité

Event Logging
This submenu allows the user to view the extreme values of some key parameters.
Meter
This function offers a possibility for the user to display three most concerned
measurements in one screen. For instance, three line voltages can be shown in one
screen in a better resolution and better view. Detailed instructions for this function can
be found in
4.2.4.
4.2.1
Overview
Details on all available measurements through RVT:
Designation
Unit
Voltage
Vrms
V
V1
V
Frequency
Hz
THDV
%
V harm. Table
V harm. chart
Current
Irms
A
I1
A
THDI
%
I harm. table
I harm. chart
Power
Cos j
PF
P
W
Q
var
S
VA
Table 1: Measurements overview
Description
Rms Voltage
Rms voltage at the
fundamental frequency
Fundamental voltage
frequency
Total harmonic voltage
distortion on voltage
Voltage harmonics displayed
in a table
Voltage harmonics displayed
in a bar graph
Rms Current
Rms current at the
fundamental frequency
Total harmonic current
distortion on current
Current harmonics displayed
in a table
Current harmonics displayed
in a bar graph
Displacement power factor
Power factor
Active power
Reactive power
Apparent power
Range
Accuracy
Up to 690Vac
± 1 %
Up to 690Vac
± 1 %
45Hz - 65Hz
± 0.5%
0 - 300%
± 1 %
2nd-49th
See later in this paragraph
2nd-49th
See later in this paragraph
Range
Accuracy
0 - 5 A
± 1 %
0 - 5 A
± 1 %
0 - 300%
± 1 %
2nd-49th
See later in this paragraph
2nd-49th
See later in this paragraph
Range
Accuracy
-1 è +1
± 0.02
-1 è +1
± 0.02
-10
9
9
W
± 2%
è10
-10
9
9
var
± 2%
è10
9
0 è10
VA
± 2%
Power Factor Controller RVT ç Measurements and Settings 25
Max value
6
10
V
6
10
V
45Hz - 75 Hz
1000 %
Max value
6
10
A
10
6
A
1000%
Max value
-1 è +1
-1 è +1
-10
9
9
W
è10
-10
9
9
var
è10
9
0 è 10
VA

Publicité

loading

Ce manuel est également adapté pour:

Rvt12Rvt12-3p