4.3.1
Manual settings (Set Mode)
The manual settings allow the user to access all the Bank, Installation, User settings and
protection/warning configurations. The user can also restore the factory setting from
this sub-menu.
Before making any settings to the controller, please make it is in Set mode. Please refer
to
3.2.4
and 4.3.1.1. for the controller mode setting and locking/unlocking.
4.3.1.1 Bank settings
start->settings->manual settings->bank settings
The Bank Settings menu includes all configuration parameters related to the bank.
Following shows the list of bank setting parameters.
V nominal: nominal bank voltage.
When a V nominal value is entered, under-voltage and overvoltage protection levels are
automatically set at 80% and 120% of V nominal.
These level values can be changed manually.
V scaling: external voltage transformer ratio.
Figure 26: Manual settings
Figure 27: Bank setting
Power Factor Controller RVT ç Measurements and Settings 35
Outputs
selection and
settings
Delays settings
Power factor