Figure 28: RVT outputs 1-6
Figure 29: RVT outputs 7-12 (Three phase model RVT12-3P)
On the right of the screen, the "Status" includes six attributes of each output:
"Fixed OFF": this output is disabled (default factory setting);
"Fixed ON": this output is enabled (the corresponding capacitor is always connected);
"1PhL1, 1Phl2, 1PhL3": this output controls a phase to neutral capacitor, which is at phase
1, 2 or 3 respectively.
"3Ph": this output controls a 3 phase capacitor.
For a Base Model RVT6/RVT12, only "Fixed OFF, Fixed ON and Enabled" are available for
the output status. An output need to be set "Enabled" before the controller switches on
or off a capacitor.
Some typical outputs setting for Three Phase Model RVT12-3P:
Typical setting one: 12 steps of single phase (phase to neutral) capacitors:
Power Factor Controller RVT ç Measurements and Settings 37