TROUBLESHOOTING AND POSSIBLE SOLUTIONS
• When a fault occurs, the red collective fault signal
LED lights up and the collective fault signal is
activated. The error code is displayed for 30 s on
the display. Thereafter the error code can be read
from the fault memory.
• Faults that only lead to switching operations once
a set time has elapsed are indicated by a fl ashing
fault alarm LED. The error code is displayed for
30 s on the display. Thereafter the error code can
be read from the fault memory.
• Self-acknowledging faults such as dry run, high
water, etc. are displayed by a fl ashing fault signal
on the main screen and can be read in the fault
memory.
• A fault on one of the connected pumps is indicat-
ed on the main screen by a fl ashing status symbol
for the corresponding pump.

10.2. Fault acknowledgement

Acknowledgement of the individual errors is via
the menu.
Select menu 6.0.0.0.
Select menu 6.1.0.0 and press the operat-
ing knob --> the error symbol fl ashes.
Turn the operating knob once to the right.
The error symbol appears marked "reset"
and fl ashes.
Press the operating knob. All faults elimi-
nated are acknowledged and the fault LED
goes out.
If the fault LED continues to be lit or fl ashes, not
all errors have been eliminated. Check the indi-
vidual errors in the fault memory, eliminate these
and reacknowledge these faults.

10.3. Fault memory

The switchgear stores the last 16 errors in the
fault memory. The log uses the FiFo principle
(First in/First out).
1.
Select menu 6.0.0.0.
2.
Select menu 6.1.0.0.
3.
Select menu 6.1.0.1.
4.
The last fault appears.
5.
Turn the operating knob to the right. You
will then scroll through the fault memory
(6.1.0.1 to 6.1.0.16).

10.4. Error codes

Fault: Rotating fi eld error
Cause: Mains connection faulty, incorrect rotating
fi eld
E06
Solution: Have the mains connection checked and
set a clockwise rotating fi eld. In case of an alter-
nating current connection, deactivate rotating fi eld
monitoring via menu 5.4.7.0!
Installation and operating instructions Wilo-Control SC-L
Fault: Leakage monitoring
Cause: The moisture probe of the connected pump
was tripped
E14.x
Remedy: See installation and operating instructions
for the connected pump, request these from Wilo
customer service
Fault: Temperature monitor for motor winding
Cause: Motor winding for the connected pump is
getting too hot
E20.x
Solution: Check operating conditions (water level,
running times etc.) and adjust these where neces-
sary, request these from Wilo customer service
Fault: Overload protection
Cause: Motor protection for the connected pump
was tripped
E21.x
Solution: Compare settings with the current data
on the rating plate for the pump; adjustments may
only be made by qualifi ed electricians or Wilo cus-
tomer service!
Fault: Level sensor faulty
Cause: No connection to the sensor
E40
Solution: Check the wire and the sensor and replace
the defective component
Fault: Dry-running protection tripped
Cause: Dry-running level reached
E62
Solution: Check the unit parameters and adjust
where necessary; Check the fl oat switches are
working correctly and replace them if necessary
Fault: High-water alarm triggered
Cause: High water level reached
E66
Solution: Check the unit parameters and adjust
where necessary; Check the fl oat switches are
working correctly and replace them if necessary
Fault: Overriding Off:
Cause: "External OFF" contact is open
E68
Remedy: Use the "External off" contact accord-
ing to the latest wiring diagram; Check settings in
menu 5.4.9.0 and adjust them if necessary
Fault: Fault on the connected pumps
Cause: No feedback from the corresponding con-
tactor
E80.x
Solution: Set the separate HAND-0-AUTO switch
for the pump shown to "Auto (A)"; Contact Wilo
customer service
Fault: Max. running time for the connected pumps
exceeded
Cause: Pump shown runs for longer than specifi ed
E85.x
in menu 5.4.6.0
Solution: Check settings in menu 5.4.6.0 and
adjust these where necessary, request these from
Wilo customer service
Fault: Plausibility error
Cause: Float switches are in incorrect sequence
E90
Solution: Check installation and connections and
adjust these where necessary
".x" = info on the relevant pump to which the
error shown refers!

10.5. Further steps for troubleshooting

If the points listed here do not rectify the fault,
contact Wilo customer service. They can help you
as follows:
• Telephone and/or written support from Wilo cus-
tomer service