Menu 5: Basic switchgear settings
No.
Description
Priority when dry run and high
water signals are present simul-
5.2.5.0
taneously**
Values: Dry Run, High Water
Factory setting: Dry Run
Signal detection for level con-
trol**
5.2.6.0
Values: Floater, Sensor
Factory setting: Sensor
5.4.0.0 Limit values
Dry run level
5.4.1.0
Value range*: 0.01 to 12.39
Factory setting: 0.12
High water alarm level
5.4.2.0
Value range*: 0.12 to 12.50
Factory setting: 1.50
High water alarm delay
5.4.4.0
Value range: 0 to 30
Factory setting: 0
Running time monitoring of indi-
vidual pumps
5.4.5.0
Values: ON, OFF
Factory setting: OFF
Max. running time of individual
pumps
5.4.6.0
Value range: 0 to 60
Factory setting: 10
Behaviour in case of mains con-
nection errors**
5.4.7.0
Values: OFF, Message, Stop
Pumps
Factory setting: Stop Pumps
Behaviour on activation of ther-
mal motor winding monitoring
5.4.8.0
and leakage detection**
Values: Auto Reset, Manu Reset
Factory setting: Auto Reset
Behaviour when "External OFF"
contact is open**
5.4.9.0
Values: Ext.Off, Alarm
Factory setting: Ext. off
5.5.0.0 Setting for signal outputs
Collective run signal (SBM)**
function
5.5.1.0
Values: Ready, Run
Factory setting: Run
Collective fault signal function**
5.5.2.0
Values: Fall, Raise
Factory setting: Raise
5.6.0.0 Pump cycling**
44
Menu 5: Basic switchgear settings
Display
No.
General pump cycling
5.6.1.0
Values: ON, OFF
Factory setting: ON
Pump cycling after time interval
5.6.2.0
Values: ON, OFF
Factory setting: OFF
Running time of base-load pump
until pump cycling
5.6.3.0
Value range: 0 to 60
Factory setting: 10
5.7.0.0 Pump kick**
Switching pump kick on/off
5.7.1.0
Values: ON, OFF
Factory setting: OFF
Interval between pump kicks
5.7.2.0
Value range: 1 to 336
Factory setting: 12
Running time of pump(s) on
pump kick
5.7.4.0
Value range: 1 to 30
Factory setting: 5
* The value range is dependent on the sensor
measuring range.
** See the function description below
6.4.2. Explanation of individual functions and settings
Menu 5.1.3.0 / GSM
This menu item is only active if the optionally
available module has been installed in the switch-
gear. Please contact Wilo customer service for
more information and for retrofi tting.
Menu 5.2.5.0 / Priority when dry run and high
water signals are present simultaneously
If the system malfunctions, it may happen that
both signals are present at the same time. In such
cases, it is necessary to stipulate which signal is
overriding:
• "Dry Run" Dry-running protection
• "High Water": High water alarm
Menu 5.2.6.0/ Signal detection for level control
The switchgear can be operated for level meas-
urement both with fl oat switches and with a level
sensor. The following options are available:
• "Floater": Float switch
• "Sensor": Level sensor
If fl oat switches are used, some of the menu
items will not be available!
Menu 5.4.7.0 / Behaviour in case of mains con-
nection errors**
This function can only be used with a 3~-mains
connection. With a 1~-mains connection, this
OPERATION AND FUNCTION
Description