Rif
Description
UNIT
Ac70
Fresh air damper request in case of regulation probe error: modulating
Fresh air damper request in case of regulation probe error: on/off
Bypass damper request in case of regulation probe error: modulating
Thermal wheel request in case of regulation probe error: modulating
Bypass damper request in case of regulation probe error: on/off
Mixing damper request in case of regulation probe error
Mixing damper request in case of regulation probe error
Exhaust damper request in case of regulation probe error
Exhaust damper request in case of regulation probe error
Ac72
Supply damper request in case of regulation probe error
Supply damper request in case of regulation probe error
Return damper request in case of regulation probe error
Return damper request in case of regulation probe error
Main coil request in case of regulation probe error
PreHeating coil request in case of regulation probe error
PostHeating coil request in case of regulation probe error
Ac74
Supply fan speed request in case of regulation probe error
Supply fan speed request in case of regulation probe error
Supply fan speed request in case of regulation probe error
Supply fan speed request in case of regulation probe error
Return fan speed request in case of regulation probe error
Supply fan speed request in case of regulation probe error
Compressor request in case of regulation probe error: BLDC
Compressor request in case of regulation probe error: On/off
Humidifi cation request in case of regulation probe error
IEC: request in case of regulation probe error
Exemple :
En cas d'erreur de la sonde de réglage du ventilateur et également d'erreur de la sonde de refoulement, le ventilateur est forcé à
la demande défi nie en cas d'erreur de sonde de refoulement.
Remarque : en cas d'erreur de la sonde d'ambiance, le réglage sera eff ectué en vérifi ant la sonde de refoulement et en main-
tenant le dernier point de consigne défi ni par l'interface utilisateur. Le décalage de réglage d'ambiance est réinitialisé.
9.25 Profi ls de fonctionnement
La commande dispose de 4 profi ls de fonctionnement, qui sont sélectionnés lors de la défi nition des plages horaires : Off (Arrêt),
Économie, Préconfort, Confort. Voir le chapitre « Interface utilisateur ». Pour chaque mode de fonctionnement, il est possible
de régler le point de consigne de température en modes chauff age et refroidissement, en fonction de la sonde de réglage sél-
ectionnée, le point de consigne de pression diff érentielle/débit d'air, le point de consigne de qualité de l'air, le point de consigne
d'humidité ambiante.
Rif
Description
UNIT
Aa03 Unit setpoints - Supply temperature - Cooling - Economy - Setpoint
Unit setpoints - Supply temperature - Heating - Economy - Setpoint
Unit setpoints - Supply temperature - Cooling - Economy - Low limit value
Unit setpoints - Supply temperature - Heating - Economy - Low limit value
Unit setpoints - Supply temperature - Cooling - Economy - High limit value 30.0
Unit setpoints - Supply temperature - Heating - Economy - High limit value 26.0
Aa06 Unit setpoints - Supply temperature - Cooling - Pre-comfort - Setpoint
Unit setpoints - Supply temperature - Heating - Pre-comfort - Setpoint
Unit setpoints - Supply temperature - Cooling - Pre-comfort - Low limit value 16.0
Unit setpoints - Supply temperature - Heating - Pre-comfort - Low limit value 18.0
Unit setpoints - Supply temperature - Cooling - Pre-comfort - High limit value 28.0
Unit setpoints - Supply temperature - Heating - Pre-comfort - High limit value 28.0
Aa09 Scheduler: confi guration - Enabled
Unit setpoints - Supply temperature - Cooling - Comfort - Setpoint
Unit setpoints - Supply temperature - Heating - Comfort - Setpoint
Unit setpoints - Supply temperature - Cooling - Comfort - Low limit value 16.0
Unit setpoints - Supply temperature - Heating - Comfort - Low limit value 18.0
Unit setpoints - Supply temperature - Cooling - Comfort - High limit value 28.0
Unit setpoints - Supply temperature - Heating - Comfort - High limit value 28.0
k.air +030220982 rel 1.1 - 31.03.2020
Dev
Min
Max
UoM Dir Modbus BACnet
0.0
0.0
100.0
%
0
0
100
%
0.0
0.0
100.0
%
0.0
0.0
100.0
%
0
0
100
%
0.0
0.0
100.0
%
0
0
100
%
0.0
0.0
100.0
%
0
0
100
%
0.0
0.0
100.0
%
0
0
100
%
0.0
0.0
100.0
%
0
0
100
%
0.0
0.0
100.0
%
50.0
0.0
100.0
%
50.0
0.0
100.0
%
0
0
3
%
0.0
0.0
100.0
%
0
0
100
%
0
0
3
%
0.0
0.0
100.0
%
0
0
100
%
0.0
0.0
100.0
%
0
0
100
%
0.0
0.0
100.0
%
0.0
0.0
100.0
%
Dev
Min
Max
UoM
28.0
LowLimVal HiLimVal
°C
18.0
LowLimVal HiLimVal
°C
18.0
0.0
HiLimVal
°C
16.0
0.0
HiLimVal
°C
LowLimVal 100.0
°C
LowLimVal 100.0
°C
26.0
LowLimVal HiLimVal
°C
20.0
LowLimVal HiLimVal
°C
0.0
HiLimVal
°C
0.0
HiLimVal
°C
LowLimVal 100.0
°C
LowLimVal 100.0
°C
FALSE
0
1
-
26.0
LowLimVal HiLimVal
°C
20.0
LowLimVal HiLimVal
°C
0.0
HiLimVal
°C
0.0
HiLimVal
°C
LowLimVal 100.0
°C
LowLimVal 100.0
°C
FRE
R/W HR1362 AV2870
R/W HR1363 PIV2871
R/W HR1364 AV2872
R/W HR1365 AV2873
R/W HR1366 PIV2874
R/W HR1367 AV2875
R/W HR1368 PIV2876
R/W HR1369 AV2877
R/W HR1370 PIV2878
R/W HR1371 AV2879
R/W HR1372 PIV2880
R/W HR1373 AV2881
R/W HR1374 PIV2882
R/W HR1375 AV2883
R/W HR1376 AV2884
R/W HR1377 AV2885
R/W HR1378 PIV2886
R/W HR1379 AV2887
R/W HR1380 PIV2888
R/W HR1381 PIV2889
R/W HR1382 AV2890
R/W HR1383 PIV2891
R/W HR1384 AV2892
R/W HR1385 PIV2893
R/W HR1386 AV2894
R/W HR1387 AV2895
Tab. 9.be
Dir Modbus BACnet
R/W HR1062
AV2572
R/W HR1063
AV2573
R/W HR1064
AV2574
R/W HR1065
AV2575
R/W HR1066
AV2576
R/W HR1067
AV2577
R/W HR1068
AV2578
R/W HR1069
AV2579
R/W HR1070
AV2580
R/W HR1071
AV2581
R/W HR1072
AV2582
R/W HR1073
AV2583
R
CS064
BV64
R/W HR1074
AV2584
R/W HR1075
AV2585
R/W HR1076
AV2586
R/W HR1077
AV2587
R/W HR1078
AV2588
R/W HR1079
AV2589
91