AUXILIARY_REGULATION
H001
Auxiliary Regulation 1 - Input selection
Auxiliary Regulation 1 - Output selection
H003
Auxiliary Regulation 1 - Dout: Error value
Auxiliary Regulation 1 - Modulating: Error value
Auxiliary Regulation 1 - Enable selection
Auxiliary Regulation 1 - Enable selection: Manual enabling
H005
Auxiliary Regulation 1 - Setpoint selection
Auxiliary Regulation 1 - Regulation setpoint
Auxiliary Regulation 1 - Modulating: Low limit
Auxiliary Regulation 1 - Dout: Diff erential
Auxiliary Regulation 1 - Modulating: High limit
Auxiliary Regulation 1 - Enable comfort auxiliary regulation
H007
Auxiliary Regulation 1 - Modulating: Kp
Auxiliary Regulation 1 - Modulating: Integral time
Auxiliary Regulation 1 - Modulating: Derivative time
Auxiliary Regulation 1 - Modulating: Dead Band
H009
Auxiliary Regulation 1 - Reverse mode
Auxiliary Regulation 1 - Cooling/Heating mode
Exemple : gestion de la résistance électrique
La résistance de dégivrage est gérée par une régulation auxiliaire, qui doit être activée. Dans ce cas, la sonde de réglage est la
sonde externe. L'activation de la résistance Marche/Arrêt est du type « chauff age direct » et évolue tel qu'illustré sur la fi gure,
pour la résistance de modulation l'action dépend des paramètres PID.
Fig. 9.al
82
Fonctions
Cooling
St
Reg_pr
diff
Heating/direct
ON
OFF
Ext_pr
diff
St
Heating/direct
100%
Max
Min
Ext_pr
diff
St
Légende
St
Point de consigne
Reg_ pr
Sonde de réglage
Max.
Valeur maximale sortie modulante
Diff
Diff érentiel
Min.
Valeur minimale sortie modulante
Dev
Min
Max
UoM Dir Modbus BACnet
0
0
13
-
0
0
1
-
FALSE 0
1
-
0.0
0.0
100.0
-
0
0
5
-
FALSE 0
1
-
0
0
4
-
20.0
- 9999.9 9999.9
-
0.0
0.0
100.0
-
20.0
0.0
999.9
-
100.0
0.0
100.0
-
FALSE 0
1
-
8.0
0.0
999.9
-
120
0
999
-
0
0
999
-
0.0
0.0
999.9
-
FALSE 0
1
-
FALSE 0
1
-
Légende
Ext_pr
Sonde externe
St
Point de consigne
Diff
Diff érentiel
R/W HR1584 PIV3079
R/W HR1585 PIV3080
R/W CS261
BV261
R/W HR1586 AV3081
R/W HR1587 PIV3082
R/W CS262
BV262
R/W HR1588 PIV3083
R/W HR980
AV2502
R/W HR1589 AV3084
R/W HR1590 AV3085
R/W HR1591 AV3086
R/W CS263
BV263
R/W HR1592 AV3087
R/W HR1593 PIV3088
R/W HR1594 PIV3089
R/W HR1595 AV3090
R/W CS264
BV264
R/W CS265
BV265