Carel k.Air large Manuel D'utilisation page 140

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

FRE
Variable
RoomTemp.PrbOk_R
RoomTemp.Alrm_R
RoomHum.Enable_W
RoomHum.Confi gured_R
RoomHum.PrbOk_R
RoomHum.Alrm_R
ExtTemp.Enable_W
ExtTemp.PrbOk_R
ExtTemp.Alrm_R
ExtHum.Enable_W
ExtHum.Confi gured_R
ExtHum.PrbOk_R
ExtHum.Alrm_R
ExhTemp.Enable_W
ExhTemp.Confi gured_R
ExhTemp.PrbOk_R
ExhTemp.Alrm_R
ExhHum.Enable_W
ExhHum.Confi gured_R
ExhHum.PrbOk_R
ExhHum.Alrm_R
AFreezeTemp.Enable_W
AFreezeTemp.Confi gured_R
AFreezeTemp.PrbOk_R
AFreezeTemp.Alrm_R
SatTemp.Enable_W
SatTemp.PrbOk_R
SatTemp.Alrm_R
SatHum.Enable_W
SatHum.Confi gured_R
SatHum.PrbOk_R
SatHum.Alrm_R
FreshAirPreHeatTemp.Enable_W
FreshAirPreHeatTemp.Confi gured_R
FreshAirPreHeatTemp.PrbOk_R
FreshAirPreHeatTemp.Alrm_R
SupplyAirP.Enable_W
SupplyAirP.Confi gured_R
SupplyAirP.PrbOk_R
SupplyAirP.Alrm_R
RetAirP.Enable_W
RetAirP.Confi gured_R
RetAirP.PrbOk_R
RetAirP.Alrm_R
AirQuality_CO2.Enable_W
AirQuality_CO2.Confi gured_R
AirQuality_CO2.PrbOk_R
AirQuality_CO2.Alrm_R
AirQuality_VOC.Enable_W
AirQuality_VOC.Confi gured_R
AirQuality_VOC.PrbOk_R
AirQuality_VOC.Alrm_R
DscgP.Enable_W
DscgP.Confi gured_R
DscgP.PrbOk_R
DscgP.Alrm_R
DscgT.Enable_W
DscgT.Confi gured_R
DscgT.PrbOk_R
DscgT.Alrm_R
SuctP.Enable_W
SuctP.Confi gured_R
SuctP.PrbOk_R
140
Tableau des variables de supervision
Description
Room temperature - Probe working correctly
Room temperature - Alarm probe broken or disconnected
Room humidity - Enable input
Room humidity - Analog input confi gured
Room humidity - Probe working correctly
Room humidity - Alarm probe broken or disconnected
Fresh air temperature - Enable input
Fresh air temperature - Probe working correctly
Fresh air temperature - Alarm probe broken or disconnected
Fresh air humidity - Enable input
Fresh air humidity - Analog input confi gured
Fresh air humidity - Probe working correctly
Fresh air humidity - Alarm probe broken or disconnected
Exhaust temperature - Enable input
Exhaust temperature - Analog input confi gured
Exhaust temperature - Probe working correctly
Exhaust temperature - Alarm probe broken or disconnected
Exhaust humidity - Enable input
Exhaust humidity - Analog input confi gured
Exhaust humidity - Probe working correctly
Exhaust humidity - Alarm probe broken or disconnected
Antifreeze temperature - Enable input
Antifreeze temperature - Analog input confi gured
Antifreeze temperature - Probe working correctly
Antifreeze temperature - Alarm probe broken or disconnected 1
Saturation temperature - Enable input
Saturation temperature - Probe working correctly
Saturation temperature - Alarm probe broken or disconnected 1
Saturation humidity - Enable input
Saturation humidity - Analog input confi gured
Saturation humidity - Probe working correctly
Saturation humidity - Alarm probe broken or disconnected
Fresh Air Pre-Heattemperature - Enable input
Fresh Air Pre-Heattemperature - Analog input confi gured
Fresh Air Pre-Heattemperature - Probe working correctly
Fresh Air Pre-Heattemperature - Alarm probe broken or
disconnected
Supply air pressure - Enable input
Supply air pressure - Analog input confi gured
Supply air pressure - Probe working correctly
Supply air pressure - Alarm probe broken or disconnected
Return air pressure - Enable input
Return air pressure - Analog input confi gured
Return air pressure - Probe working correctly
Return air pressure - Alarm probe broken or disconnected
CO2 sensor - Enable input
CO2 sensor - Analog input confi gured
CO2 sensor - Probe working correctly
CO2 sensor - Alarm probe broken or disconnected
VOC sensor - Enable input
VOC sensor - Analog input confi gured
VOC sensor - Probe working correctly
VOC sensor - Alarm probe broken or disconnected
Discharge pressure - Enable input
Discharge pressure - Analog input confi gured
Discharge pressure - Probe working correctly
Discharge pressure - Alarm probe broken or disconnected
Discharge temperature - Enable input
Discharge temperature - Analog input confi gured
Discharge temperature - Probe working correctly
Discharge temperature - Alarm probe broken or disconnected 1
Suction pressure - Enable input
Suction pressure - Analog input confi gured
Suction pressure - Probe working correctly
Dim Modbus
BACnet
1
DI021
BV479
1
DI022
BV480
1
DI023
BV481
1
DI024
BV482
1
DI025
BV483
1
DI026
BV484
1
DI027
BV485
1
DI029
BV487
1
DI030
BV488
1
DI031
BV489
1
DI032
BV490
1
DI033
BV491
1
DI034
BV492
1
DI035
BV493
1
DI036
BV494
1
DI037
BV495
1
DI038
BV496
1
DI039
BV497
1
DI040
BV498
1
DI041
BV499
1
DI042
BV500
1
DI043
BV501
1
DI044
BV502
1
DI045
BV503
DI046
BV504
1
DI047
BV505
1
DI049
BV507
DI050
BV508
1
DI051
BV509
1
DI052
BV510
1
DI053
BV511
1
DI054
BV512
1
DI055
BV513
1
DI056
BV514
1
DI057
BV515
1
DI058
BV516
1
DI059
BV517
1
DI060
BV518
1
DI061
BV519
1
DI062
BV520
1
DI063
BV521
1
DI064
BV522
1
DI065
BV523
1
DI066
BV524
1
DI067
BV525
1
DI068
BV526
1
DI069
BV527
1
DI070
BV528
1
DI071
BV529
1
DI072
BV530
1
DI073
BV531
1
DI074
BV532
1
DI075
BV533
1
DI076
BV534
1
DI077
BV535
1
DI078
BV536
1
DI079
BV537
1
DI080
BV538
1
DI081
BV539
DI082
BV540
1
DI083
BV541
1
DI084
BV542
1
DI085
BV543
k.air +030220982 rel 1.1 - 31.03.2020

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

K.air miniC.pcoeK.air

Table des Matières