Description
UNIT
Ae66
Pre-heat coil step 4 - Working hours
Pre-heat coil step 4 - Working hours threshold (1000hrs)
Pre-heat coil step 4 - Working hours left to the maintenance
Pre-heat coil step 4 - Working hours reset
Ae69
Re-heat coil pump 1 - Working hours
Re-heat coil pump 1 - Working hours threshold (1000hrs)
Re-heat coil pump 1 - Working hours left to the maintenance
Re-heat coil pump 1 - Working hours reset
Ae72
Re-heat coil pump 2 - Working hours
Re-heat coil pump 2 - Working hours threshold (1000hrs)
Re-heat coil pump 2 - Working hours left to the maintenance
Re-heat coil pump 2 - Working hours reset
Ae75
Re-heat coil analog output - Working hours
Re-heat coil analog output - Working hours threshold (1000hrs)
Re-heat coil analog output - Working hours left to the maintenance
Re-heat coil analog output - Working hours reset
Ae78
Re-heat coil step 1 - Working hours
Re-heat coil step 1 - Working hours threshold (1000hrs)
Re-heat coil step 1 - Working hours left to the maintenance
Re-heat coil step 1 - Working hours reset
Ae81
Re-heat coil step 2 - Working hours
Re-heat coil step 2 - Working hours threshold (1000hrs)
Re-heat coil step 2 - Working hours left to the maintenance
Re-heat coil step 2 - Working hours reset
Ae83
Re-heat coil step 3 - Working hours
Re-heat coil step 3 - Working hours threshold (1000hrs)
Re-heat coil step 3 - Working hours left to the maintenance
Re-heat coil step 3 - Working hours reset
Ae84
Re-heat coil step 4 - Working hours
Re-heat coil step 4 - Working hours threshold (1000hrs)
Re-heat coil step 4 - Working hours left to the maintenance
Re-heat coil step 4 - Working hours reset
Ae99
Reset total working hours counter of all devices
Error communication for Import/Export blocks
Error communication for Import/Export blocks
10.1.2 B. Fans
Rif
Description
FANS
Ba01
Only for mask usage
Fan regulation type (0: Static pressure; 1: Air fl ow; 2: Fixed speed)
Supply fan confi guration error
Ba03
Enable air quality regulation for fans
Enable air quality regulation for fresh air OR mixing damper
Air Quality - Fans PID parameters - Proportional gain
Air Quality - Fans PID parameters - Integral time
Ba06
Air fl ow switch check type: 0=none; 1=common; 2=separated;
Air fl ow check type
Number of retry after return or supply air fl ow switch error detected
during start up procedure before turn off the unit
Timeout for air fl ow switch detection (seconds)
Air fl ow switch alarm delay time in running mode (s)
Ba09
Air fl ow check pressure threshold
Ba12
Fan post ventilation time
Enabling the selection of the temperature regulation for the fans
Enable fan temperature regulation
Ba15
Enable fan regulation in case of FreeCooling/FreeHeating
Ba18
Enable night minimum ventilation
Night minimum ventilation: starting hour
Night minimum ventilation: starting minutes
Night minimum ventilation: ending hour
Night minimum ventilation: ending minutes
k.air +030220982 rel 1.1 - 31.03.2020
Dev
Min
Max
UoM
0
0
99
h
30
0
99
-
-
0
99
h
-
0
1
-
0
0
99
h
30
0
99
-
-
0
99
h
-
0
1
-
0
0
99
h
30
0
99
-
-
0
99
h
-
0
1
-
0
0
99
h
30
0
99
-
-
0
99
h
-
0
1
-
0
0
99
h
30
0
99
-
-
0
99
h
-
0
1
-
0
0
99
h
30
0
99
-
-
0
99
h
-
0
1
-
0
0
99
h
30
0
99
-
-
0
99
h
-
0
1
-
0
0
99
h
30
0
99
-
-
0
99
h
-
0
1
-
-
0
1
-
-
0
9
-
-
0
9
-
Dev
Min
Max
UoM
TRUE
0
1
-
2
0
2
-
-
0
1
-
FALSE
0
1
-
FALSE
0
1
-
1.0
0.0
999.9
-
60
0
999
-
0
0
3
-
0
0
2
-
3
0
9
-
15
1
999
s
3
0
999
s
50.0
0.0
9999.0
Pa
10
0
600
s
-
0
1
-
FALSE
0
1
-
FALSE
0
1
-
FALSE
0
1
-
22
0
23
h
0
0
59
min
6
0
23
h
0
0
59
min
FRE
Dir Modbus BACnet
R
IR477
PIV3808
R/W HR1441
PIV2949
R
IR479
PIV3809
R/W HR1442
PIV2950
R
IR481
PIV3810
R/W HR1443
PIV2951
R
IR483
PIV3811
R/W HR1444
PIV2952
R
IR485
PIV3812
R/W HR1445
PIV2953
R
IR487
PIV3813
R/W HR1446
PIV2954
R
IR489
PIV3814
R/W HR1447
PIV2955
R
IR491
PIV3815
R/W HR1448
PIV2956
R
IR493
PIV3816
R/W HR1449
PIV2957
R
IR495
PIV3817
R/W HR1450
PIV2958
R
IR497
PIV3818
R/W HR1451
PIV2959
R
IR499
PIV3819
R/W HR1452
PIV2960
R
IR501
PIV3820
R/W HR1453
PIV2961
R
IR503
PIV3821
R/W HR1454
PIV2962
R
IR505
PIV3822
R/W HR1455
PIV2963
R
IR507
PIV3823
R/W HR1456
PIV2964
R/W HR1457
PIV2965
R
IR509
IV3824
R
IR509
IV3824
Tab. 10.a
Dir Modbus BACnet
R
DI701
BV1159
R/W HR1491
PIV2992
R
DI702
BV1160
R/W CS245
BV245
R
CS289
BV289
R/W HR1492
AV2993
R/W HR1493
PIV2994
R/W HR1494
PIV2995
R/W HR1495
PIV2996
R/W HR1496
PIV2997
R/W HR1497
PIV2998
R/W HR1498
PIV2999
R/W HR1499
AV3000
R/W HR1500
PIV3001
R
DI703
BV1161
R/W CS246
BV246
R/W CS247
BV247
R/W CS248
BV248
R/W HR1501
PIV3002
R/W HR1502
PIV3003
R/W HR1503
PIV3004
R/W HR1504
PIV3005