10.1.9 I. IEC
Rif
Description
IEC
I001
IEC: PID parameters - Proportional gain
IEC: PID parameters - Integral time
I005
IEC: Return humidity activation threshold
IEC: Return humidity activation diff erential
I010
IEC: Exhaust humidity limit threshold
IEC: Exhaust humidity limit proportional gain
IEC: Exhaust humidity limit integral time
I015
IEC: Fresh air damper maximum limitation
10.1.10
J. VDI
Rif
Description
VDI
Ja01
VDI Inactivity startup activation delay
VDI Inactivity startup duration
VDI high saturation humidity threshold
VDI high saturation humidity diff erential
Ja02
VDI Type: 0: Standard; 1: Custom
Enable of the VDI function
Month selection variable
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
Enable of the VDI function
Month selection variable
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
Ja03
Enable of the VDI function
Month selection variable
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
Enable of the VDI function
Month selection variable
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
Ja06
Enable of the VDI function
Month selection variable
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
Enable of the VDI function
Month selection variable
Reset timings after the inspection
Ja09
Enable of the VDI function
Month selection variable
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
Enable of the VDI function
Month selection variable
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
Ja12
Enable of the VDI function
Month selection variable
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
Enable of the VDI function
Month selection variable
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
Ja15
Enable of the VDI function
Month selection variable
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
Enable of the VDI function
Month selection variable
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
Ja18
Enable of the VDI function
Month selection variable
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
Enable of the VDI function
Month selection variable
Reset type (FALSE: Blocker Alarm; TRUE: Warning)
k.air +030220982 rel 1.1 - 31.03.2020
Dev
Min
Max
UoM
8.0
0.0
999.9
-
120
0
999
-
75.0
0.0
100.0
%rh
2.0
0.0
20.0
%rh
95.0
0.0
100.0
%rh
10.0
0.0
999.9
-
60
0
999
s
0.0
0.0
100.0
%
Dev
Min
Max
UoM
48
0
65535
h
5
0
65535
min
80.0
0.0
99.0
%rh
2.0
0.0
99.0
%rh
0
0
1
-
TRUE
0
1
-
4
0
5
-
TRUE
0
1
-
TRUE
0
1
-
3
0
5
-
TRUE
0
1
-
TRUE
0
1
-
1
0
5
-
TRUE
0
1
-
TRUE
0
1
-
3
0
5
-
TRUE
0
1
-
TRUE
0
1
-
2
0
5
-
TRUE
0
1
-
TRUE
0
1
-
2
0
5
-
-
0
1
-
TRUE
0
1
-
2
0
5
-
TRUE
0
1
-
TRUE
0
1
-
2
0
5
-
TRUE
0
1
-
TRUE
0
1
-
1
0
5
-
TRUE
0
1
-
TRUE
0
1
-
1
0
5
-
TRUE
0
1
-
TRUE
0
1
-
1
0
5
-
TRUE
0
1
-
TRUE
0
1
-
1
0
5
-
TRUE
0
1
-
TRUE
0
1
-
2
0
5
-
TRUE
0
1
-
TRUE
0
1
-
3
0
5
-
TRUE
0
1
-
FRE
Dir Modbus BACnet
R/W HR1646
AV3141
R/W HR1647
PIV3142
R/W HR1648
AV3143
R/W HR1649
AV3144
R/W HR1650
AV3145
R/W HR1651
AV3146
R/W HR1652
PIV3147
R/W HR1653
AV3148
Tab. 10.i
Dir Modbus BACnet
R/W HR1686
PIV3181
R/W HR1687
PIV3182
R/W HR1688
AV3183
R/W HR1689
AV3184
R/W HR1690
PIV3185
R/W CS296
BV296
R/W HR1691
PIV3186
R/W CS297
BV297
R/W CS298
BV298
R/W HR1692
PIV3187
R/W CS299
BV299
R/W CS300
BV300
R/W HR1693
PIV3188
R/W CS301
BV301
R/W CS302
BV302
R/W HR1694
PIV3189
R/W CS303
BV303
R/W CS304
BV304
R/W HR1695
PIV3190
R/W CS305
BV305
R/W CS306
BV306
R/W HR1696
PIV3191
R/W CS307
BV307
R/W CS308
BV308
R/W HR1697
PIV3192
R/W CS309
BV309
R/W CS310
BV310
R/W HR1698
PIV3193
R/W CS311
BV311
R/W CS312
BV312
R/W HR1699
PIV3194
R/W CS313
BV313
R/W CS314
BV314
R/W HR1700
PIV3195
R/W CS315
BV315
R/W CS316
BV316
R/W HR1701
PIV3196
R/W CS317
BV317
R/W CS318
BV318
R/W HR1702
PIV3197
R/W CS319
BV319
R/W CS320
BV320
R/W HR1703
PIV3198
R/W CS321
BV321
R/W CS322
BV322
R/W HR1704
PIV3199
R/W CS323
BV323
Tableau des paramètres