Carel k.Air large Manuel D'utilisation page 118

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

FRE
10.1.3 C. Dampers
Rif
Description
DAMPERS
Ca01
Damper opening time
Ca03
Enable air quality regulation for fresh air OR mixing damper
Air Quality - Dampers PID parameters - Proportional gain
Air Quality - Dampers PID parameters - Integral time
Ca06
Fresh air damper - Minimum regulation value
Fresh air damper - Maximum regulation value
Ca09
Mixing air damper - Minimum regulation value
Mixing air damper - Maximum regulation value
Ca12
Enable dampers regulation in case of FreeCooling/FreeHeating
10.1.4 D. Coils
Rif
Description
COILS
Da01
Main coil confi guration
Main coil steps number
Compressor type (FALSE: ON/OFF; TRUE: BLDC)
Enable EVD emb management
Da03
Cooling coil PID parameters - Proportional gain
Cooling coil PID parameters - Integral time
Da06
Heating coil PID parameters - Proportional gain
Heating coil PID parameters - Integral time
Da09
Dehumidifi cation PID parameters - Proportional gain
Dehumidifi cation PID parameters - Integral time
Dehumidifi cation PID parameters - Derivative time
Maximum dehumidifi cation off set
Da12
Heating coil request during antifreeze off status
Da18
Cooling coil request during antifreeze off status
Da21
Cooling/Heating coil pumps number
Cooling/Heating coil pumps fl ow check startup delay
Cooling/Heating coil pumps fl ow check run delay
Cooling/Heating coil pumps enable antilock function
Cooling/Heating coil pumps rotation time
Da24
Coil fl oating valve:Running time
Db01 PreHeating coil steps number
Db03 Pre heating PID parameters - Proportional gain
Pre heating PID parameters - Integral time
Db06 PreHeating coil request during antifreeze off status
Db09 PreHeating coil pumps number
PreHeating coil pumps fl ow check startup delay
PreHeating coil pumps fl ow check run delay
PreHeating coil pumps enable antilock function
PreHeating coil pumps rotation time
Db12 Coil fl oating valve:Running time
Dc01
PostHeating coil steps number
Dc03
Post heating PID parameters - Proportional gain
Post heating PID parameters - Integral time
Dc06
PostHeating coil request during antifreeze off status
Dc09
Post Heating coil pumps number
Re Heating coil pumps fl ow check startup delay
ReHeating coil pumps fl ow check run delay
Re Heating coil pumps enable antilock function
Re Heating coil pumps rotation time
Dc12
Coil fl oating valve:Running time
118
Tableau des paramètres
Dev
Min
Max
UoM
120
0
65535
s
FALSE
0
1
-
1.0
0.0
999.9
-
60
0
999
-
0.0
0.0
100.0
%
100.0
0.0
100.0
%
0.0
0.0
100.0
%
100.0
0.0
100.0
%
FALSE
0
1
-
Dev
Min
Max
UoM
2
0
2
-
1
1
4
-
TRUE
0
1
-
TRUE
0
1
-
8.0
0.0
999.9
-
120
0
999
-
8.0
0.0
999.9
-
120
0
999
-
8.0
0.0
999.9
-
120
0
999
-
0
0
999
-
2.0
-99.9
99.9
K
50.0
0.0
100.0
%
50.0
0.0
100.0
%
0
0
2
-
15
0
999
s
5
0
999
s
TRUE
0
1
-
24
0
999
h
180
1
999
s
1
1
4
-
8.0
0.0
999.9
-
120
0
999
-
50.0
0.0
100.0
%
0
0
2
-
15
0
999
s
5
0
999
s
TRUE
0
1
-
24
0
999
h
180
1
999
s
1
1
4
-
8.0
0.0
999.9
-
120
0
999
-
50.0
0.0
100.0
%
0
0
2
-
15
0
999
s
5
0
999
s
TRUE
0
1
-
24
0
999
h
180
1
999
s
Dir Modbus BACnet
R/W HR1639
PIV3134
R/W CS289
BV289
R/W HR1640
AV3135
R/W HR1641
PIV3136
R/W HR1642
AV3137
R/W HR1643
AV3138
R/W HR1644
AV3139
R/W HR1645
AV3140
R/W CS290
BV290
Tab. 10.c
Dir Modbus BACnet
R/W HR1654
PIV3149
R/W HR1655
PIV3150
R/W CS291
BV291
R/W CS292
BV292
R/W HR1656
AV3151
R/W HR1657
PIV3152
R/W HR1658
AV3153
R/W HR1659
PIV3154
R/W HR1660
AV3155
R/W HR1661
PIV3156
R/W HR1662
PIV3157
R/W HR1663
AV3158
R/W HR1664
AV3159
R/W HR1665
AV3160
R/W HR1666
PIV3161
R/W HR1667
PIV3162
R/W HR1668
PIV3163
R/W CS293
BV293
R/W HR1669
PIV3164
R/W HR1914
PIV3940
R/W HR1670
PIV3165
R/W HR1671
AV3166
R/W HR1672
PIV3167
R/W HR1673
AV3168
R/W HR1674
PIV3169
R/W HR1675
PIV3170
R/W HR1676
PIV3171
R/W CS294
BV294
R/W HR1677
PIV3172
R/W HR1914
PIV3940
R/W HR1678
PIV3173
R/W HR1679
AV3174
R/W HR1680
PIV3175
R/W HR1681
AV3176
R/W HR1682
PIV3177
R/W HR1683
PIV3178
R/W HR1684
PIV3179
R/W CS295
BV295
R/W HR1685
PIV3180
R/W HR1914
PIV3940
Tab. 10.d
k.air +030220982 rel 1.1 - 31.03.2020

Publicité