Rif
Description
UNIT
Ac12
Fresh air damper type (0: On/Off ; 1: Modulating)
Exhaust air damper type (0: On/Off ; 1: Modulating)
Mixing air damper type (0: On/Off ; 1: Modulating)
Supply air damper type (0: On/Off ; 1: Modulating)
Return air damper type (0: On/Off ; 1: Modulating)
Bypass damper type (0: On/Off ; 1: Modulating)
Ac16
Filters confi guration
HEPA Filter confi guration (0: None; 1: Filt 1; Filt 1 & 2)
Ac18
Regulation type (0: Supply only; 1:Return only; 2: Room only; 3: Return
+ Supply; 4: Room + Supply; 5: Disabled)
Ac20
Regulation set point off set: proportional gain
Regulation set point off set: integral time
Ac22
Machine type (0: COOLING; 1: HEATING; 2: COOL/HEAT)
Machine type cooling/heating enabled
Unit cooling heating mode confi guration
Ac24
Cooling external temperature threshold
Heating external temperature threshold
Ac28
Cooling/Heating coil water temperature cooling threshold
Cooling/Heating coil water temperature heating threshold
Ac30
Main coil: water temperature out of range warning delay time
Coil water temperature: action confi guration
Ac32
Humidifi cation/Dehumidifi cation: Control probe
Humidifi cation/Dehumidifi cation: Control type
Ac34
Dehumidifi cation: Regulation type
Dehumidifi cation: enable kwater dew point calculation
Ac36
Humidifi cation/Dehumidifi cation: Regulation band
Humidifi cation/Dehumidifi cation: Regulation change delay time
Ac11
Freecooling activation delta
Freeheating activation delta
Ac40
Free cooling PID parameters - Proportional gain
Free cooling PID parameters - Integral time
Ac42
Free heating PID parameters - Proportional gain
Free heating PID parameters - Integral time
Ac44
Enable warm up procedure during start up state
Low external temperature threshold for the activation of warm up
procedure
Settable delay between return and supply fan activation (seconds).
To be used only when warm up procedure is disabled
Warm up delay time
Warm up fan activation delay time
Ac46
For mask usage
Supply fan request for automatic warm up
For mask usage
Enable return fan
For mask usage
Return fan request for automatic warm up
For mask usage
Ac48
PreHeating coil warm up request
Main coil warm up request
PostHeating coil warm up request
Bypass damper warm up request
Thermal wheel warm up request
For mask usage
Ac50
For mask usage
Supply fan request for automatic switch on when warm up
is not enabled
For mask usage
Ac52
Antifreeze type (0: NONE; 1: Ext.Temp.; 2: AFreeze Temp.;
3: DigitalInput)
Ac54
Antifreeze temperature threshold
Antifreeze ending delta
Ac56
Anti freeze warning delay time
Antifreeze alarm delay time
Enable antifreeze during off state
Ac58
Prevent antifreeze threshold
Ac60
Low supply temperature threshold
Low supply temperature alarm delay time at start up
Low supply temperature alarm delay time at unit in run mode
k.air +030220982 rel 1.1 - 31.03.2020
Dev
Min
Max
UoM
0
0
2
-
0
0
2
-
0
0
2
-
0
0
2
-
0
0
2
-
0
0
1
-
0
0
6
-
0
0
2
-
5
0
5
-
5.0
0.0
999.9
-
150
0
999
s
2
0
2
-
-
0
1
-
0
0
6
-
28.0
-99.9
99.9
°C
18.0
-99.9
99.9
°C
15.0
-99.9
99.9
°C
25.0
-99.9
99.9
°C
5
1
999
min
0
0
2
-
0
0
2
-
0
0
1
-
0
0
1
-
FALSE
0
1
-
20.0
1.0
99.0
%rh
5
0
99
min
3.0
0.0
20.0
K
3.0
0.0
20.0
K
8.0
0.0
999.9
-
120
0
999
-
8.0
0.0
999.9
-
120
0
999
-
FALSE
0
1
-
-1.0
-99.0
99.0
°C
15
1
999
s
15
1
60
s
15
0
600
s
1
0
3
-
30.0
0.0
100.0
%
0
0
100
-
FALSE
0
1
-
0
0
3
-
30.0
0.0
100.0
%
0
0
100
-
0.0
0.0
100.0
-
0.0
0.0
100.0
-
0.0
0.0
100.0
-
0.0
0.0
100.0
-
0.0
0.0
100.0
%
0
0
100
-
2
0
3
-
25.0
0.0
100.0
%
100
0
100
-
0
0
3
-
2.0
-50.0
20.0
°C
3.0
0.0
15.0
K
30
0
999
s
5
0
999
s
FALSE
0
1
-
5.0
-99.9
99.9
°C
16.0
0.0
25.0
°C
999
0
65535
s
600
0
65535
s
FRE
Dir Modbus BACnet
R/W HR1299
PIV2807
R/W HR1300
PIV2808
R/W HR1301
PIV2809
R/W HR1302
PIV2810
R/W HR1303
PIV2811
R/W HR1304
PIV2812
R/W HR1305
PIV2813
R/W HR1306
PIV2814
R/W HR1307
PIV2815
R/W HR1308
AV2816
R/W HR1309
PIV2817
R/W HR1310
PIV2818
R
DI700
BV1158
R/W HR1311
PIV2819
R/W HR1312
AV2820
R/W HR1313
AV2821
R/W HR1314
AV2822
R/W HR1315
AV2823
R/W HR1316
PIV2824
R/W HR1317
PIV2825
R/W HR1318
PIV2826
R/W HR1319
PIV2827
R/W HR1320
PIV2828
R/W CS227
BV227
R/W HR1321
AV2829
R/W HR1322
PIV2830
R/W HR1323
AV2831
R/W HR1324
AV2832
R/W HR1325
AV2833
R/W HR1326
PIV2834
R/W HR1327
AV2835
R/W HR1328
PIV2836
R/W CS228
BV228
R/W HR1329
AV2837
R/W HR1330
PIV2838
R/W HR1331
PIV2839
R/W HR1332
PIV2840
R/W HR1333
PIV2841
R/W HR1334
AV2842
R/W HR1335
PIV2843
R
CS225
BV225
R/W HR1336
PIV2844
R/W HR1337
AV2845
R/W HR1338
PIV2846
R/W HR1339
AV2847
R/W HR1340
AV2848
R/W HR1341
AV2849
R/W HR1342
AV2850
R/W HR1343
AV2851
R/W HR1344
PIV2852
R/W HR1345
PIV2853
R/W HR1346
AV2854
R/W HR1347
PIV2855
R/W HR1348
PIV2856
R/W HR1349
AV2857
R/W HR1350
AV2858
R/W HR1351
PIV2859
R/W HR1352
PIV2860
R/W CS229
BV229
R/W HR1353
AV2861
R/W HR1354
AV2862
R/W HR1355
PIV2863
R/W HR1356
PIV2864
Tableau des paramètres