2.3
Reference conditions in accordance with EN29104
Fluid temperature
20 °C ± 2 K
Ambient temperature
20 °C ± 2 K
Auxiliary power
Nominal voltage in accordance with type plate U
Warm-up phase
30 min.
Straight pipe section
Inlet > 10 x DN
outlet > 5 x DN
Measurement deviation from reference conditions
(pulse output)
Fig. 2:
Measurement deviation for standard equipment:
Flow Q > 0.07 Q
Flow Q ≤ 0.07 Q
Measurement deviation for equipment with special calibration
Flow Q > 0.07 Q
Flow Q ≤ 0.07 Q
For Q
D184B112U04
FXL5000 (Miniflow)

Performance characteristics

10
5
4
3
2
1
0
0
Measurement deviation of FXL5000 (Miniflow) measuring system
: ± 3 % of rate
maxDN
: 0.0021 Q
maxDN
: ± 1.5 % of rate
maxDN
: 0.00105 Q
maxDN
(see table below)
maxDN
DN
Q
maxDN
10
50 l/min
15
100 l/min
25
300 l/min
50
1200 l/min
± 1 %, frequency f ± 1 %
N
0.5 0.7
1.0
m/s
maxDN
maxDN