Register tables
10
Register tables
The following contains an overview of the available Modbus registers. The table contains all relevant information, such as addresses of
the registers, their functions and specification of whether the registers are read-only, write-only or read/write. This information forms the
basis for the correct setup and use of Modbus communication with the device.
10.1
Access: Read/Write
The data format for all registers is UINT16.
Register
Register
Address
Address
(dec)
(hex)
2
0x2
3
0x3
3
0x3
3
0x3
10.2
Access: Read
The data format for all registers is UINT16.
Register
Register
Description
Address
Address
(dec)
(hex)
16
0x10
System
pressure
17
0x11
Filling level
18
0x12
Digital
outputs
18
0x12
Digital
outputs
18
0x12
Digital
outputs
18
0x12
Digital
outputs
19
0x13
Digital inputs
20
0x14
Fault
messages 1
20
0x14
Fault
messages 1
20
0x14
Fault
messages 1
20
0x14
Fault
messages 1
20
0x14
Fault
messages 1
23
0x17
Warnings 1
23
0x17
Warnings 1
23
0x17
Warnings 1
23
0x17
Warnings 1
23
0x17
Warnings 1
23
0x17
Warnings 1
23
0x17
Warnings 1
23
0x17
Warnings 1
23
0x17
Warnings 1
24
0x18
Warnings 2
24
0x18
Warnings 2
30 — English
Description
Bezeichnung
Pressure
Druckvorgabe
specification
für P0
for P0
Switch over the
Betriebsmodus
operating mode
umschalten
Switch over the
Betriebsmodus
operating mode
umschalten
Switch over the
Betriebsmodus
operating mode
umschalten
Bezeichnung
Unit
Systemdruck
bar
Füllstand
%
Digitale Ausgänge
-
Digitale Ausgänge
-
Digitale Ausgänge
-
Digitale Ausgänge
-
Digitale Eingänge
-
Störmeldungen 1
-
Störmeldungen 1
-
Störmeldungen 1
-
Störmeldungen 1
-
Störmeldungen 1
-
Warnungen 1
-
Warnungen 1
-
Warnungen 1
-
Warnungen 1
-
Warnungen 1
-
Warnungen 1
-
Warnungen 1
-
Warnungen 1
-
Warnungen 1
-
Warnungen 2
-
Warnungen 2
-
Reflexomat RSC Smart — 21.10.2025-Rev. C
Unit
Bit Address
bar
-
-
Bit 0 = 1 (Dec =
1)
-
Bit 1 = 1 (Dec =
2)
-
Bit 2 = 1 (Dec =
4)
Bit Address
Meaning
-
In 1/100 bar
-
0 - 100 %
Bit 1 = 1
Compressor 1 ON
Bit 3 = 1
Overflow valve 1 open
Bit 4 = 1
Make-up valve open
Bit 6 = 1
Message Group alarm ok
Bit 3 = 1
Water meter
Bit 3 = 1
Below minimum pressure
Bit 4 = 1
Low water 1
Bit 9 = 1
Pressure measurement
fault
Bit 10 = 1
Level measurement fault
Bit 12 = 1
longer than 4 hours in
STOP mode
Bit 1 = 1
Maximum level exceeded
Bit 2 = 1
Compressor runtime
exceeded
Bit 3 = 1
Make-up time exceeded
Bit 4 = 1
Make-up cycles exceeded
Bit 5 = 1
Maximum pressure
exceeded
Bit 6 = 1
Make-up quantity
exceeded
Bit 10 = 1
Make-up valve leaking
Bit 12 = 1
Calibration incorrect
Bit 15 = 1
Maintenance requested
Bit 1 = 1
Softening, replace
cartridge
Bit 5 = 1
Conductivity too high
(optional!)
Meaning
Bedeutung
In 1/10 bar
In 1/10 bar
STOP
STOP
AUTO
AUTO
MANUAL
MANUELL
Bedeutung
In 1/100 bar
0 - 100 %
Kompressor 1 EIN
Überströmventil 1 AUF
Nachspeiseventil AUF
Meldung: Sammelstörung ok
Wasserzähler
Minimaler Druck
unterschritten
Wassermangel 1
Druckmessung gestört
Niveaumessung gestört
Länger als 4 Stunden im STOP-
Modus
Maximales Niveau
überschritten
Kompressor Laufzeit
überschritten
Nachspeisezeit überschritten
Nachspeisezyklen
überschritten
Maximaler Druck überschritten
Nachspeisemenge
überschritten
Nachspeiseventil undicht
Nullabgleich fehlerhaft
Wartungsanforderung
Enthärtung, Patrone tauschen
Leitfähigkeit zu hoch (Option!)