Télécharger Imprimer la page

Reflex omat RSC Smart AT8300A Mode D'emploi Original page 21

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 34
CAUTION
Risk of injury due to pressurised liquid
If installation, removal or maintenance work is not carried out correctly, there is
a risk of burns and other injuries at the connection points, if pressurised hot
water or hot steam suddenly escapes.
Ensure proper installation, removal or maintenance work.
Ensure that the system is de-pressurised before performing installation,
removal or maintenance work at the connection points.

Note!
Equipment parts with a safety function in respect of water-side pressure
limiting according to the Pressure Equipment Directive 2014/68/EU and
temperature limiting according to the Pressure Equipment Directive
2014/68/EU are not supplied.
The operator is responsible for on-site provision of water-side pressure
and temperature protection.

Note!
When installing the on-site safety valve, the operator must ensure that
there is no danger during blow-off.
4
Description of the device
4.1
Description
The Reflexomat is a compressor-controlled pressure maintenance system. The
main applications are glycol circuits with up to 50% glycol fraction, heating circuits
and cooling circuits.
Vessel size nominal volumes:
• 200l
• 300l
• 400l
• 500l
• 600l
The control unit is factory-installed on the expansion vessel.
All electric and air connections between control unit and primary vessel are
pre-installed.
4.2
Overview
1
"SV" safety valve
2
"RSC Smart" control unit
Compressor
Controller
"Reflex Control Smart"
3
"RG" primary vessel
4.3
Identification
4.3.1
Type plate
The type plate provides information about the manufacturer, the year of
manufacture, the manufacturing number and the technical data.
4
"LIS" level measurement
5
System connection with "EC"
hose
6
Sleeve for membrane rupture
detector
7
Display for pressure/ level
Reflexomat RSC Smart — 21.10.2025-Rev. C
Information on the type plate
Type
Serial No.
min. / max. allowable pressure PS
max. allowable flow temperature of
system
min. / max. working temperature TS
Year of manufacture
max. system pressure
min. operating pressure set up on
site
4.4
Function
1
Make-up with water e.g. using Servitec S
2
Control unit
3
Primary vessel as expansion vessel
WC Make-up line
PIS Pressure sensor
SV
Safety valve
PV
Solenoid valve with silencer
LIS Weight measuring cell for level measurement
EC
Expansion line
Expansion vessel
A butyl bladder divides the interior of the vessel into an air space and a water
space. This prevents the ingress of atmospheric oxygen into the expansion water.
The primary vessel is connected to the air side control unit and connected
hydraulically to the system circuit. Pressure relief is provided on the air side by the
vessel's "SV" safety valve.
Control unit
The control unit comprises a compressor and the "Reflex Control Smart" controller.
Via the primary vessel, the pressure is measured using the "PIS" pressure sensor
and the water level using the "LIS" weight measuring cell and the values are then
displayed on the control unit and via the app,  9 "Controller",  27.

Note!
Additional equipment for topping up water,  4.6 "Optional equipment
and accessories",  22.
4.5
Scope of delivery
The scope of delivery is described in the shipping document and the content is
shown on the packaging.
Immediately after receipt of the goods, please check the shipment for
completeness and damage. Please notify us immediately of any transport damage.
Description of the device
Meaning
Device name
Serial number
Minimum/maximum permissible pressure
Maximum permissible flow temperature
of the system
Min./max. operating temperature (TS)
Year of manufacture
Max. system pressure
Minimum operating pressure, set on-site
loading