Reflex omat RSC Smart AT8300A Mode D'emploi Original page 29

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 34
ER
Alarm
Code
05
Compressor run time
[1] Auto LED flashes
[4] Stop LED flashes
[5] Error LED flashes
[2] Pressure LED flashes
[3] Level LED off
06
Make-up time
[1] Auto LED lights up
[5] Error LED lights up
[3] Level LED flashes
07
Make-up cycles
[5] Error LED lights up
[4] Stop LED lights up
[3.3] Level LED lights up
08
Pressure measurement
[1] Auto LED off
[4] Stop LED flashes
[5] Error LED flashes
[2] Pressure LED flashes
09
Filling level measurement
[1] Auto LED off
[4] Stop LED flashes
[5] Error LED flashes
[3] Level LED flashes
10
Maximum pressure
[1] Auto LED lights up
[2] Pressure LED flashes
[5] Error LED lights up
11
Make-up quantity
15
Make-up valve
19
Stop ˃ 4 hours
[4] Stop LED lights up
[5] Error LED flashes
20
Max. make-up quantity
21
Maintenance recommended
[1] Auto LED lights up
[5] Error LED lights up
24
Softening/demineralisation
Causes
Maximum compressor run time exceeded:
Air side leak.
Compressor has no power.
Set max. make-up time has been exceeded:
Water loss in the system.
Automatic make-up not connected.
Make-up output insufficient.
Make-up hysteresis too high.
Number of set max. make-up cycles has been
exceeded:
Leakage in the system.
Controller receives incorrect signal.
Controller receives incorrect signal from the
weight measuring cell.
Set value (P
-0.3 bar) exceeded:
Sv
Air side solenoid valve does not blow off.
Compressor runs continuously.
Specified make-up quantity has been exceeded
Severe water loss in the system.
Contact water meter measures without make-up
request
Device is in Stop mode for more than 4
hours.
Max. set make-up quantity exceeded
Maintenance interval exceeded.
Soft water capacity used up
Reflexomat RSC Smart — 21.10.2025-Rev. C
Remedy
Check the water loss and correct, if
necessary.
Seal any leak in the air system.
Check functioning of "PV" air side solenoid
valve.
Check functioning of compressor.
Check the set values.
Check automatic make-up.
Check water level.
Connect make-up line.
Seal any leakage in the system.
Check the set value.
If necessary, manually add water.
Check system for leakage.
Check the plug connection at the pressure
sensor.
Check functioning of the pressure sensor.
Compare the values from the app with the
pressure gauge
Check the cable for damage.
Check the plug connection at the weight
measuring cell.
Check the functioning of the weight
measuring cell.
Check the cable for damage.
Check the set values.
Check system-side water connection.
Check functioning of air side solenoid valve.
Clean the silencer of the air-side solenoid
valve.
Check the compressor relay.
Check system for leakage.
Check system for leakage.
Clean make-up valve.
Replace make-up valve (if necessary).
Reset using the SmartControl app.
Set make-up quantity correctly.
Carry out maintenance.
Reset maintenance counters in the app.
Replace the cartridge (Fillsoft).
Controller
Alarm reset
"Service"
-
-
-
"Service"
-
-
-
"Service"
-
"App"
-
loading