Tabele registrov
10.2
Access: Read
Podatkovni format (Data Format) za vse registre je UINT16.
Register
Register
Description
Address
Address
(dec)
(hex)
16
0x10
System
pressure
17
0x11
Filling level
18
0x12
Digital outputs
18
0x12
Digital outputs
18
0x12
Digital outputs
18
0x12
Digital outputs
19
0x13
Digital inputs
20
0x14
Fault messages
1
20
0x14
Fault messages
1
20
0x14
Fault messages
1
20
0x14
Fault messages
1
20
0x14
Fault messages
1
23
0x17
Warnings 1
23
0x17
Warnings 1
23
0x17
Warnings 1
23
0x17
Warnings 1
23
0x17
Warnings 1
23
0x17
Warnings 1
23
0x17
Warnings 1
23
0x17
Warnings 1
23
0x17
Warnings 1
24
0x18
Warnings 2
24
0x18
Warnings 2
26
0x1A
Operating hours
(High-Word)
27
0x1B
Operating hours
(Low-Word)
30
0x1E
Water meter
(High-Word)
31
0x1F
Water meter
(Low-Word)
33
0x21
System type
36
0x24
Operating mode
36
0x24
Operating mode
36
0x24
Operating mode
38
0x26
Conductivity
122 — Slovenščina
Oznaka
Unit
Bit Address
Sistemski tlak
bar
-
Nivo polnjenja
%
-
Digitalni izhodi
-
Bit 1 = 1
Digitalni izhodi
-
Bit 3 = 1
Digitalni izhodi
-
Bit 4 = 1
Digitalni izhodi
-
Bit 6 = 1
Digitalni vhodi
-
Bit 3 = 1
Sporočila o
-
Bit 3 = 1
motnjah 1
Sporočila o
-
Bit 4 = 1
motnjah 1
Sporočila o
-
Bit 9 = 1
motnjah 1
Sporočila o
-
Bit 10 = 1
motnjah 1
Sporočila o
-
Bit 12 = 1
motnjah 1
Opozorila 1
-
Bit 1 = 1
Opozorila 1
-
Bit 2 = 1
Opozorila 1
-
Bit 3 = 1
Opozorila 1
-
Bit 4 = 1
Opozorila 1
-
Bit 5 = 1
Opozorila 1
-
Bit 6 = 1
Opozorila 1
-
Bit 10 = 1
Opozorila 1
-
Bit 12 = 1
Opozorila 1
-
Bit 15 = 1
Opozorila 2
-
Bit 1 = 1
Opozorila 2
-
Bit 5 = 1
Obratovalne ure
h
-
(High-Word)
Obratovalne ure
h
-
(Low-Word)
Vodni števec
l
-
(High-Word)
Vodni števec
l
-
(Low-Word)
Tip naprave
-
-
Stanje delovanja
-
Bit 0 = 1
naprave
Stanje delovanja
-
Bit 1 = 1
naprave
Stanje delovanja
-
Bit 2 = 1
naprave
Prevodnost
μS/cm
-
Reflexomat RSC Smart — 21.10.2025-Rev. C
Meaning
Bedeutung
v 1/100 bar
v 1/100 bar
0 - 100 %
0 - 100 %
Compressor 1 ON
Kompresor 1 je „VKL."
Overflow valve 1 open
Prelivni ventil 1 je ODPRT
Make-up valve open
Ventil za napajanje je ODPRT
Message Group alarm ok
Sporočilo: Zbirna motnja je v
redu
Water meter
Vodni števci
Below minimum pressure
Vrednost je pod minimalnim
tlakom
Low water 1
Pomanjkanje vode 1
Pressure measurement
Merjenje tlaka je moteno
fault
Level measurement fault
Merjenje nivoja je moteno
longer than 4 hours in
Dlje kot 4 ure v ustavitvenem
STOP mode
obratovanju.
Maximum level exceeded
Maksimalni nivo je prekoračen
Compressor runtime
Čas teka kompresorja je
exceeded
prekoračen
Make-up time exceeded
Čas napajanja je prekoračen
Make-up time exceeded
Cikli napajanja so prekoračeni
Maximum pressure
Maksimalni tlak je prekoračen
exceeded
Make-up količina je
Dodajna količina je
presežena
prekoračena
Make-up valve leaking
Ventil za napajanje ni tesen
Calibration incorrect
Ničelna primerjava ni pravilna
Maintenance requested
Zahteva po vzdrževanju
Softening, replace
Mehčanje, menjajte patrono
cartridge
Conductivity too high
Prevodnost je previsoka
(optional!)
(možnost!)
Compressor 1
Kompresor 1
Compressor 1
Kompresor 1
Accumulated sum Water
Dotečene vsote v litrih
meter in litres
Accumulated sum Water
Dotečene vsote v litrih
meter in litres
0x0: n.d.
0x0: n.d.
=0x1: Variomat
=0x1: Variomat
=0x2: Variomat Giga
=0x2: Variomat Giga
=0x3: Reflexomat
=0x3: Reflexomat
=0x4: Servitec Magcontrol
=0x4: Servitec Magcontrol
=0x5: Servitec
=0x5: Servitec Levelcontrol
Levelcontrol
=0x6: Servitec_S
=0x6: Servitec_S
=0x7: Servitec_Mini
=0x7: Servitec_Mini
=0x8: Greenbox
=0x8: Greenbox
=0x9: Fillcontrol
=0x9: Fillcontrol
=0xB (Dec =11): Servimat
=0xB (Dec =11): Servimat
Manual
ročno
Stop
Stop (Zaustavitev)
Auto
Auto (Avtomatsko)
(Only for "Conductivity
(Samo pri možnosti
monitoring" option)
„nadziranje prevodnosti")