Super Digital Inverter
7
ELECTRICAL WORK
1. Remove valve cover screw.
2. Pull the valve cover downward to remove it.
Piping cover
Indoor/outdoor
connecting wires
Power wire
EN
All manuals and user guides at all-guides.com
Valve cover
17
Wiring between Indoor Unit and Out-
door Unit
The dashed lines show on-site wiring.
(Main circuit)
Input power
L
220-240 V~,
50 Hz
N
Outdoor unit
Earth
Leakage
breaker
•
Connect the indoor/outdoor connecting wires to the
identical terminal numbers on the terminal block of each
unit.
Incorrect connection may cause a failure.
For the air conditioner, connect a power wire with the
following specifications.
Model RAV-
Power supply
Maximum running current
Installation fuse rating
Power wire
Indoor/outdoor connecting
wires
CAUTION
•
Wrong wiring may cause a burn-out of some electrical
parts.
•
Be sure to use the cord clamps attached to the product.
•
Do not damage or scratch the conductive core or inner
insulator of the power and inter-connecting wires when
peeling them.
•
Use the power and Inter-connecting wires with specified
thicknesses, specified types and protective devices
required.
(Indoor/outdoor
connecting wires)
1
1
2
2
Remote
3
3
controller
Indoor unit
SP40, SP45, SP56
220-240 V~, 50 Hz
15 A
16 A (all types can be used)
H07 RN-F or 60245 IEC 66
2
(2.5 mm
or more)
H07 RN-F or 60245 IEC 66
2
(1.5 mm
or more)