Network Configuration Information Frame; Keep Alive Frame - ADEUNIS sigfox ANALOG Guide Utilisateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

sigfox ANALOG - Guide utilisateur / User guide version V2.0.0
• Bytes 2 to 4: register 328, high threshold of channel B sensor
• Bytes 5 to 7: register 329, high hysteresis of channel B sensor
In the example in grey this gives:
• Bytes 2 to 4=0x7A1200=8,000,000 in decimal: register 328, the value of the high threshold for channel B is:
8,000,000 µV i.e. 8V
• Bytes 5 to 7=0x0F4240=100,000 in decimal: register 329, the value of the high hysteresis for channel B is:
1,000,000µV i.e. 1V
FR
0
1
Code
Status
0x14
Cf Status
0x14
0xA2
Description of the frame:
EN
• Bytes 2 to 4: register 330, low threshold of channel B sensor
• Bytes 5 to 7: register 331, low hysteresis of channel B sensor
In the example in grey this gives:
• Octets 2 à 4=0x2DC6C0=3 000 000 en décimal : registre 330, la valeur du seuil bas pour la voie B est : 3 000
000 µV soit 3V
• Octets 5 à 7=0x0F4240=1 000 000 en décimal : registre 331, la valeur de l'hystérésis bas pour la voie B est :
1 000 000µV soit 1V
4.1.3

Network configuration information frame

During the passage into operation mode (from the Park or Command Mode), the following frame (0x20) represen-
ting the network configuration of the product is transmitted:
0
1
Code
Status
0x20
Cf Status
0x20
0xA2
Description of the frame:
• Byte 2: registre 320, number of repetitions
In the example in grey this gives:
• Byte 2=0x02 : the number of repetitions will be 2
4.1.4

Keep Alive frame

This frame (0x30) is transmitted only in the event mode at the frequency defined by register 300.
0
1
Code
Status
0x30
Cf Status
0x30
0xA2
Description of the frame:
• Byte 2: Type of the sensor on channel A. Configured by the user (register 320).
• Bytes 3 to 5: Value measured on channel A.
• If the type of sensor is 0-10V: The value is expressed in µV
• If the type of sensor is 4-20mA: The value is expressed in nA
• Byte 6: Type of the sensor on channel B. Configured by the user (register 322).
• If the type of sensor is 0-10V: The value is expressed in µV
• If the type of sensor is 4-20mA: The value is expressed in nA
• Bytes 7 to 9: Value measured on channel B.
2
3
4
S330
0x2DC6C0
2
3
4
S202
X
X
0x02
2
3
4
Sensor
Value read on the channel C
type
sensor
0x01
0x0C3500
5
6
7
PAYLOAD
S331
0x0F4240
5
6
7
PAYLOAD
X
X
X
5
6
7
PAYLOAD
Sensor
Value read on the channel B
type
0x01
8
9
10
X
X
X
8
9
10
X
X
X
8
9
10
X
sensor
0x4C4B40
Page
70
of 86

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Arf8191aaArf8191ba

Table des Matières