4.2.1 Product configuration request frame

This frame allows to inform the product via the network that it must resend the product configuration uplink frame (0x10).
0
Code
0x01
FR

4.2.2 Network configuration request frame

This frame allows to inform the product via the network that it must resend the network configuration uplink frame (0x20).
0
Code
0x02
EN

4.2.3 Value request frame of specific registers

This frame (0x40) makes it possible to inform the product via the network that it must transmit the values of the registers requested.
Frame 0x40:
0
Code
0x40
CONF ID 1
Description of the frame:
Bytes 1 to n: CONF ID X (8 bits): index of the register to send. The corresponding register is 300 + CONF ID X value.
For example, if CONF ID 1 = 0x14 (20 decimal), the transmitter will return the S320 register value.
The associated uplink is code 0x31 (see section 4.1.5 for details).
IMPORTANT: the user can specify several CONF IDs in his downlink frame but it is up to him to verify that according to the protocol, the size of
the data available in a downlink will be large enough to contain all the desired data. Otherwise, the application will send only the first values.

4.2.4 Frame for updating the value of specific registers

This frame (0x41) allows to change the value of requested registers.
0
Code
0x41
Description of the frame :
Byte 1: CONF ID1 (8bits) : index of the first register to change. The corresponding register is 300 + value of CONF IDX. For example, if
CONF ID1 = 0x14 (hexadecimal, so 20 decimal), the product will change the value of register number 320.
Byte 2: value to assign to CONFID1 : in this example, its value has a size of 1 byte
Byte 3: CONFID2 (8bits) : index of the second register to change. The corresponding register is 300 + value of CONFIDX.
Bytes 4 and 5: value to assign to CONFID2 : in this example, its value has a size of 2 bytes
...
Following the sending of the downlink 0x41, the associated uplink 0x33 will be immediately returned (see detail in section 4.1.6). If the update
of the register (s) went well, the product will save and start its restart procedure automatically. In addition, the Configuration bit of the status
byte (see section 4.1.1.2) will be set to 1 in the next scheduled upstream frame (periodic, alarm or life frame).
1
2
X
X
1
2
X
X
1
2
CONF ID 2
1
2
CONFID1
CONFID1 value
DISTRIBUTED BY TEXIM EUROPE
3
4
PAYLOAD
X
X
3
4
PAYLOAD
X
X
3
4
PAYLOAD
CONF ID 3
X
3
4
PAYLOAD
CONFID2 value
CONFID2
(MSB)
5
6
X
X
5
6
X
X
5
...
X
X
5
...
CONFID2 value
...
(LSB)
7
X
7
X
n
CONF ID n
n
CONFID7 value
Page
74