5.3. Replacing the battery

When the low battery indicator is enabled (indicator in the frame or flashing of the red LED), it is possible to change the internal battery of the
unit.
It is important to use a battery of the same reference, use FANSO ER18505H or FANSO ER18505H soldered with a 36 mm cable with a molex
51021 connector depending if you have a product with a battery-pack.
FR
EN
-

5.4. Cabling Digital Input 2 via the terminal block

+
In order to be able to combine a dry contact sensor with the device and thus benefit from its Digital
Input 2, it is necessary to connect the sensor to the terminal block of the card.
Connection procedure for the wires:
1. Open the unit (paragraph 5.1)
2. Plug the two wires into each notch of the terminal block
3. Break the element of the casing so as to pass the wire onto the back of the casing
4. Configure the digital input 2 alarm (section 3.3.1.04)
5. Close the unit
6. Restart the device with the button as for a first start
After this procedure the device will behave as during a first start (paragraph 5.7)
E.g.:
The Sigfox SmartBuilding COMFORT device can easily be combined with a cabled door contact via the
terminal block (Digital Input 2). Thus, positioned next to the door of a secure room under control, the
device will be able to send an alarm every time the door is opened/closed and thus enable the security
manager or the building manager to verify compliance with the security requirements on the site.
DISTRIBUTED BY TEXIM EUROPE
Procedure for changing the battery:
1.Open the unit (paragraph 5.1)
2. Remove the battery and replace it with the new one respect-
ing the polarity as indicated on the electronic card if you have a
product without connector, otherwise just clip the connector.
3. Close the unit
4
- If the device was in "REPLI" mode before changing the
battery, press the button. After this procedure the device will
behave as during a first start (paragraph 5.7).
- If the device was not in "REPLI" mode when the battery was
changed then it will automatically detect it after sending a few
frames and erase the low battery indicators (status and LED).