6.2

Electrical connections

A switch or an omnipolar cut-off switch with a contact opening of at least 3 mm must be
installed on the mains power line; put the cut-off switch in OFF position and disconnect any
buffer batteries before performing any cleaning or maintenance operations.
Ensure that an adequate residual current circuit breaker with a 0.03 A threshold and a suitable
overcurrent cut-out are installed upstream the electrical installation in accordance with best
practices and in compliance with applicable legislation.
For power supply, use a H07RN-F 3G1.5 type electric cable and connect it to the terminals L
(brown), N (blue),
Strip the insulation from the ends of the power cable wires which will be connected to the
terminal and secure the cable with the cable retainer.
Connections to the electrical distribution network and to any other low-voltage conductors
in the external section to the electrical panel must be on an independent path and
separate from the connections to the command and safety devices (SELV = Safety Extra Low
Voltage).
Make sure that the mains power conductors and the accessory wires (24 V) are separated.
The cables must be double insulated, strip them near the relevant connection terminals and
lock them with clamps [B] (not supplied).
L N
AP1-CM-CH1
M
AP2-CM-CH2
M
(yellow/green), located inside the control panel box.
DESCRIPTION
Mains power supply 230 V~ ±10% connection.
Connection to ROGER MOTOR 1.
The gate open and/or gate closed stop limit switches may be connected to the control
unit. When a limit switch is activated, power is cut to the motor opening/closing the gate.
Connect the gate open limit switch to terminals AP1-CM, and connect the gate closed
limit switch to terminals CH1-CM.
To connect the limit switches directly to the control unit, refer to chapter 6.
N.B.: the value of the capacitor between AP1 and CH1 is indicated in the instructions for
the motor installed.
Connection to ROGER MOTOR 2.
The gate open and/or gate closed stop limit switches may be connected to the control
unit. When a limit switch is activated, power is cut to the motor opening/closing the gate.
Connect the gate open limit switch to terminals AP2-CM, and connect the gate closed
limit switch to terminals CH2-CM.
To connect the limit switches directly to the control unit, refer to chapter 6.
N.B.: the value of the capacitor between AP2 and CH2 is indicated in the instructions for
the motor installed.
53