Configuring the Heat Pump Heating System
System-specific parameters
The heating curve end point should be set
according to the design of the heating system.
This should be done by entering the maximum
return flow temperature, which is the product of
the maximum calculated flow temperature
minus the temperature difference in the heating
system (spread).
Parallel shift of the set heating curve for heating
circuit 1. By pressing the arrow buttons once,
the heating curve is shifted by 1 °C upwards
(hotter) or downwards (colder)..
Sets the desired return flow set temperature
when fixed setpoint control is selected
Sets the desired room set temperature and I
ratio when room temperature regulation is
selected
Sets the minimum return flow temperature
when room temperature regulation is selected
Different maximum temperatures are
permissible for panel and radiator heating
systems. The upper limit of the return flow set
temperature can be set between 25 °C and
70 °C.
The return set temperature hysteresis forms
the neutral zone for operation of the heat pump.
If the temperature "Return set temperature plus
hysteresis" is reached, the heat pump switches
itself off. If the temperature "Return set
temperature minus hysteresis" is reached, the
heat pump switches itself on.
settings to lower the heating characteristic
curve of heating circuit 1
Sets the times during which the temperature in
heating circuit 1 is to be lowered.
Sets the temperature value by which the
heating characteristic curve of heating circuit 1
is to be lowered when the temperature is
lowered
For each day of the week, it is possible to select
whether Time1, Time2, no time or both times
are to be active when the temperature is
lowered. Operations to lower the temperature
that exceed a weekday are activated or
deactivated at the end of each day accordingly.
Settings to raise the heating characteristic
curve of heating circuit 1
Sets the time during which the temperature in
heating circuit 1 is to be raised.
Sets the temperature value by which the
heating characteristic curve of heating circuit 1
is to be raised when the temperature is raised.
Setting range
Display
20 °C
Heating circuit 1
... 30 °C ...
Regulation according
to external
70 °C
temperature
Indicator bar
Heating circuit 1
Regulation according
to external
temperature
15 °C
Heating circuit 1
... 40 °C ...
Heating circuit 1 fixed
setpoint
60 °C
15,0 °C / 001
Heating circuit 1
... 20.0 °C .../ ...60 ...
Heating circuit 1
room regulation
30,0 °C / 999
15 °C
Heating circuit 1
... 20 °C ...
Heating circuit 1
room regulation
30 °C
25 °C
Heating circuit 1
... 50 °C ...
70 °C
0.5K
Heating circuit 1
... 2 K ...
5K
Heating circuit 1
00:00
Heating circuit 1
...
23:59
0K
Heating circuit 1
...
19K
N
Heating circuit 1
T1
T2
Y
Heating circuit 1
00:00
Heating circuit 1
...
23:59
0K
Heating circuit 1
...
19K
6.1
EN-13