2.2.2 Periodic transmission with history

The product allows the accumulation of several successive meter values before the periodic transmission of the set of values according to the
following scheme:
FR
EN
The parameters associated with this mode of operation are:
Enabling and Configuring inputs (register 320)
History configuration (register S321)
Anti-bounce timer period (registers S322)
A complete list of the registers can be found in paragraph 3.4.
Eg:
Registre
S320
S321
S322
Product in standby
Historical
No
period rea-
ched
?
Yes
Number of
No
recorded
values rea-
ched ?
Yes
Send frame 0x48
Value encoding
Hexadecimal
Hexadecimal
Hexadecimal
Detected
and valida-
ted pulse
?
Yes
Counting
of the impulse
Value
Result
0x39
Channel A :
Activated
Meter other than gas
Tamper input activated
Channel B :
Activated
Gas meter
Tamper input disabled
0x02
Channels A and B : historical mode with backup of the
counters every hour and transmission every 24h so 24
values per counter
0x57
Anti-rebound :
Channel A = 500ms
Channel B = 100ms
No
Page
64