WMBUS TEMP - Guide utilisateur / User guide version V2.0.0

2.1.4 REPLI mode

The product enters this very low consumption mode following the detection of a level of battery that is too low. In this mode the product wakes
up every 5 seconds to make the red LED flash twice.
The replacement of the battery (if the product is a replaceable battery version) followed by the application of the magnet takes the product out
of this mode to return it to the operating mode.

2.2. Operating modes

2.2.1 Periodic transmission

The product allows the measurement and the periodic transmission of the values of the sensors according to the following diagram:
Product on stand-by
Sampling
period reached
?
Internal
temperature measure-
ment and storage
External
temperature measure-
ment and storage
Transmission
period reached
?
Average internal tempe-
rature samples
Average external tempe-
rature samples
Send frame 0x43
The product allows you to define a super-sampling to send, not an instantaneous
value but, an averaged value at the time of the transmission period defined.
The settings associated with this mode of operation are:
• The transmission period (register 301).
• Potential user identifiers for the sensors (registers 320 and 322).
• The super-sampling factor (register 333).
No
A complete list of the registers can be found in paragraph 3.4.
E.g.:
Yes
No
In this example:
• The product transmits every hour (6x10min=60min)
• As the super-sampling factor is 4, there will be a measurement and a storage
operation every 60/4=15 minutes
Yes
• The value sent will therefore be an average of 4 temperatures collected every 15
minutes
Caution: averaging can reduce the importance of some peaks (maximum values) if
the temperature changes quickly.
Take care also over the values of the period and the super-sampling because they
have an impact on the consumption of the product. In the extreme a 10 minute
transmission periodicity and a factor of super-sampling of 10 leads to a measure-
ment every minute.
Register Value
Value
encoding
S301
Decimal
6
S320
Hexadecimal 0xD0
S322
Hexadecimal 0x80
S333
Decimal
4
Result
Periodic mode with a period of
6x10min = 60 minutes
Identifier of the internal sensor set
to 0xD
Identifier of the external sensor set
to 0x8
The number of samples to be
measured and stored between two
transmissions is 4
FR
EN
49 of 77