Periodic Transmission - ADEUNIS DRY CONTACTS IP68 Guide Utilisateur

Lorawan 863-870
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

DRY CONTACTS IP68 LoRaWAN 863-870 - Guide utilisateur / User guide version V1.0.0

2.4.2 Periodic transmission

The product allows the measurement and the periodic transmission of the values of the sensors according to the following diagram:
No
The settings associated with this mode of operation are:
• The transmission period (register 301).
• The configurations of the different digital inputs (registers 320 to 323)
• Threshold to overpass before sending the frame (registers 324 to 327)
Example:
Register
S301
S320
S322
S321
S323
S324
S325
S326
S327
In this example the product send a frame every 10 minutes with the number of events on channel 1 (openings or closings), the number of clos-
ings on channel 3 and the number o openings on channel 4. Further more, the event mode is activated on the channel 1, the frame is sent also
when 10 events are detected on the channel 1.
IMPORTANT NOTE: For each 0X40 frame sent (for an event or periodically) the counters are set to 0 for all the channels.
Product in standby
Period
reached?
Yes
Send frame 0x40
Value encoding
Decimal
Hexadecimal
Hexadecimal
Hexadecimal
Hexadecimal
Decimal
Decimal
Decimal
Decimal
Change on
digital input
?
Yes
Counting
event
Value
Result
60
Periodic mode with a period of 60 x 10 seconds = 10
minutes
0x43
Configuration of the channel 1:
• Count of the openings or closings on the dry contact
• Debounce time* of 100 ms
0x00
Configuration of the channel 2:
• Deactivated
• No debounce time*
0xB1
Configuration of the channel 3:
• Count closings only
• Debounce time* of 20 seconds
0x32
Configuration of the channel 4:
• Count openings only
• Debounce time* of 50 ms
10
The frame is sent after 10 changes of state on channel 1
0
Deactivated (periodical only)
0
Deactivated (periodical only)
0
Deactivated (periodical only)