Counting Time Alarm Frame - ADEUNIS DRY CONTACTS IP68 Guide Utilisateur

Lorawan 863-870
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

DRY CONTACTS IP68 LoRaWAN 863-870 - Guide utilisateur / User guide version V1.0.0

2.4.5 Counting time alarm frame

The device enables the transmission of an alarm frame (0x41) if it detects an event duration higher than the threshold defined by the user.
Product in standby
FR
Change of
state on the
input ?
EN
YES
Count the time spent
in this state
Duration
overpassed
?
YES
Send frame 0x41
Associated parameters for this alarm mode are:
• Thresholds for alarm detection on each channel (registers 340 to 343)
• Configurations of the inputs (registers 320 to 323)
Example:
Register
Encoding
NO
S340
Decimal
S341
Decimal
S342
Decimal
S343
Decimal
In this example the frame 0x41 is sent if an event is longer than 3 minutes on Channel 1 or longer
than 15 minutes on Channel 2 or longer than 30 minutes on Channel 3.
IMPORTANT NOTE: Alarm is sent only one time after event overpass the threshold. If the event
persists the alarm is not repeated. However, if a new event is detected then the threshold is triggered
again.
NO
Value
Result
0x03
Event on Channel 1 longer than 3 minutes
0x0f
Event on Channel 2 longer than 15 minutes
0x1e
Event on Channel 3 longer than 30 minutes
0x00
No alarm
52 of 63

Publicité

Table des Matières
loading

Table des Matières