2.5.3 Output commands of the product, change the output state during a defined time

The product enables to change the state of all or one channel configured as an output during in a defined time (as a temporized relay) remotely
through a 0x07 downlink frame:
FR
Product in standby
EN
For this mode the associated parameters are:
• Configuration of the channels (registers 320 to 323)
• State of the channel configured as output (registers 330 to 333)
Example :
Register
S320
S321
S322
S323
S330
S331
S332
S333
In this example the channel 2 the output is configured with a state closed by default (output=1). Thanks to the 0x07 downlink frame the user
can change the state of the output during a defined timing (in tenth of seconds) then the device will turn the output back into the default state.
In this example the user can change the output state to opened during 60 seconds. After 1 minute the device will switch the output to the
closed state.
IMPORTANT NOTE: the state of the output is lost if the product died because of low battery.
No
Event or pe-
Yes
Send a frame 0xXX
riod reached
?
Encoding value
Hexadecimal
Hexadecimal
Hexadecimal
Hexadecimal
Decimal
Decimal
Decimal
Decimal
Receive 0x07
Output channel
turn back to its
previous state
Value
Result
0x73
Configuration of the channel 1:
• Count openings and closings of the dry contact
• Debounce time* of 1 second
0x04
Configuration of the channel 2:
• Output
• No debounce time*
0xB4
Configuration of the channel 3:
• Count closings only
• Debounce time* of 20 seconds
0x32
Configuration of the channel 4:
• Count openings only
• Debounce time* of 50 ms
0
Channel 1 configured as an input
1
Channel 2 configured as an output: state closed
0
Channel 3 configured as an input
0
Channel 4 configured as an input
Update the state of
the output channel
Non
Timing
reached ?