ADEUNIS WMBUS Pulse Guide Utilisateur page 75

Transceiver pulse interfaces
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

WMBUS Pulse - Guide utilisateur / User guide version V2.2.0
S320
Channels configuration (A
and B)
S321
History configuration (chan-
nels A and B)
S322
Anti-bounce filter period
(pulse minimum width) (chan-
nels A and B)
Hexadecimal
Default value: 0x11
For channel A :
Bit 0 : channel A activation
• Value 0: channel deactivated
• Value 1: channel activated
Bit 1 : meter type channel A (pull-up activation)
• Value 0: meter other than Gas (pull-up deactivated)
• Value 1: Gas meter (pull-up activated)
Bit 2 : Reserved
Bit 3 : tamper input channel A
• Value 0: deactivated
• Value 1: activated
For channel B :
Bit 0 : channel B activation
• Value 0: channel deactivated
• Value 1: channel activated
Bit 1 : meter type channel B (pull-up activation)
• Value 0: meter other than Gas (pull-up deactivated)
• Value 1: Gas meter (pull-up activated)
Bit 2 : Reserved
Bit 3 : tamper input channel B
• Value 0: deactivated
• Value 1: activated
Hexadecimal
Default value : 0x00
Bits 0 to 2: History configuration
Value 0: no history
Value 1: history period set to 10min / transmit period set to 1 hour
Value 2: history period set to 1 hour / transmit period set to 24 hours
Hexadecimal
Default value: 0x22
Bits 0 to 3 : anti-bounce filter period - channel A
Value 0: deactivated
Value 1: 1 ms
Value 2: 10 ms
Value 3: 20 ms
Value 4: 50 ms
Value 5: 100 ms
Value 6: 200 ms
Value 7: 500 ms
Value 8: 1 s
Value 9: 2 s
Value A: 5 s
Value B: 10 s
Value C to F : reserved
Bits 4 to 7 : anti-bounce filter period - channel B
Value 0: deactivated
Value 1: 1 ms
Value 2: 10 ms
Value 3: 20 ms
Value 4: 50 ms
Value 5: 100 ms
Value 6: 200 ms
Value 7: 500 ms
Value 8: 1 s
Value 9: 2 s
Value A: 5 s
Value B: 10 s
Value C to F : reserved
FR
EN
Page
75
of 99

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Pulse atexArf8230eaArf8230haArf8043xx

Table des Matières