5.3

Pneumatic connection of the Top Control Continuous

Connect the air supply (3..7 bar, instrument air, oil, water and duster) to port 1 (Fig. 5.1).
Mount the exhaust air pipe or noise reducer on port 3 (Fig. 5.1).
Supply pressure
connector (inscription: 1)
Bild 5.1: Fluidic connections of the TopControl
NOTE
The pressure supply must exceed the pressure required by the pneumatic actuator and must exceed at
least 0.5 to 1 bar.
This is to ensure that the control process in the upper ranges of the actuator will not become negative due
to a lower pressure difference.
Keep the pressure supply variations within the most restricted limits (max. ±10 %).
Higher variations reduce the reliability of the measured parameters within the AUTOTUNE procedure.
5.4

Electrical connection

Various options are available for electrical connection
Multipole connection
Terminals (with cable glands)
QUICKON connection
ATTENTION!
A screw with a nut is available in the connecting module for connection of the technical earth (TE). In
order to comply with the EMC requirements connect this screw to a good earthing point with a short
length cable (max. 30 cm).
108
Outlet air connector
(inscription: 3)
Operating instructions no. 800607